Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
373
7.8
Malfunction of Thermistor for Outdoor Air (R1T)
Remote
Controller
Display
H9
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
The abnormal detection is based on current detected by current sensor.
Malfunction
Decision
Conditions
When the outdoor air temperature sensor has short circuit or open circuit.
Supposed
Causes
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PCB (A1P)
Troubleshooting
The alarm indicator is displayed when the fan only is being used also.
∗
Refer to thermistor resistance / temperature characteristics table on P398.
(Q0428)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PCB.
(3.5k
Ω
~
360k
Ω
)
Connector is
connected to outdoor
PCB(A1P).
Replace outdoor unit PCB A1P.
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R1T)
YES
YES
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...