Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
375
7.10
Malfunction of Thermistor (R2T) for Suction Pipe
Remote
Controller
Display
J5
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the suction pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R2T) for outdoor unit suction pipe
Defect of outdoor unit PCB (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P398.
(Q0430)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R2T) from the outdoor
unit PCB.
(3.5k
Ω
~
360k
Ω
)
Replace outdoor unit PCB A1P.
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor R2T.
YES
YES
Connector
is connected to outdoor
unit PCB.
(A1P)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...