Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
377
7.12
Malfunction of Receiver Gas Pipe Thermistor (R5T)
Remote
Controller
Display
J9
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by receiver gas pipe thermistor
(= Subcooling heat exchanger gas pipe thermistor).
Malfunction
Decision
Conditions
When the receiver gas pipe thermistor is short circuited or open.
Supposed
Causes
Faulty receiver gas pipe thermistor (R5T)
Faulty outdoor unit PCB
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P398.
(Q0445)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R5T) from outdoor unit
PCB normal.
(3.5 k
Ω
to
360 k
Ω
)
Replace outdoor unit PCB (A1P).
Connect thermistor and turn on
again.
NO
NO
Replace the thermistor (R5T).
YES
YES
Is the
connector for
receiver gas pipe
thermistor connected to
outdoor unit PCB
(A1P)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...