Troubleshooting for Outdoor Unit
Si18-525B
380
Troubleshooting
7.15
Malfunction of Inverter Radiating Fin Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 99°C.
Supposed
Causes
Actuation of fin thermal (Actuates above 99°C)
Defect of inverter PCB
Defect of fin thermistor
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P398.
(Q0436)
Resistance
check of the radiator fin
thermistor
Measure the resistance of the
radiator fin thermistor.
Defect of power unit radiation.
•
Intake port is clogged
•
Radiator fin is dirty
•
Outdoor temperature is high
NO
Replace the thermistor.
YES
Abnormal
Is reset possible?
Reset and operate.
Normal
Replace the inverter PCB
NO
YES
Temperature
of the radiator fin rises.
Actuates at min.
99 ˚C
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...