Troubleshooting for Outdoor Unit
Si18-525B
390
Troubleshooting
Troubleshooting
Repair wiring.
NO
Is
connection
wire connected
between the connector
X205A and X25A?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(Q0442)
NO
YES
YES
YES
Replace the inverter PCB.
Does
the voltage
between terminals P
and N gradually rise to
283VDC after
turning
on?
The
voltage
between the P and N
terminals is 400VDC and
190VDC or more when
the compressor is
running.
NO
Is the
power supply voltage
at the connector X1A of
outdoor PCB
side?
Is the
power supply voltage
applied at LB and NB
on the noise filter
PCB?
Monitor field power
supply.
Check the transmission
wiring between the
outdoor unit PCB and
inverter unit.
NO
Replace the inverter PCB.
YES
NO
Replace the inverter PCB.
Turn on again.
YES
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...