Troubleshooting for Outdoor Unit
Si18-525B
394
Troubleshooting
7.27
Refrigerant System not Set, Incompatible Wiring/Piping
Remote
Controller
Display
UF
Applicable
Models
AII BP unit models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Failure to execute wiring check operation
Defect of BP unit PCB
Failure to open the stop valve
Troubleshooting
Note:
Test operation may not be successful if carried out after the outdoor unit has been off for more
than 12 hours, or if it is not carried out after running all connected indoor units in the fan mode
for at least an hour.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(Q0388)
Replace the BP unit PCB.
Is the
electronic
expansion valve coil
disconnected?
Retry to test operation
Is "UF" displayed again?
Test operation may not have
been carried out successfully.
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PCB for 5 seconds.
Correct the electronic
expansion coil.
NO
YES
NO
YES
Is Indoor-BP
and BP-outdoor unit
transmission wiring
normal?
Open stop valve.
YES
NO
Are the stop
Valves opened?
∗
The unit will not run for up to
12 minutes.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...