Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
395
7.28
Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
AII indoor unit models
All BP unit models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Defect of indoor unit PCB
Defect of BP unit PCB
Defect of outdoor unit PCB (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(Q0389)
NO
YES
YES
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PCB for 5 seconds.
Normal
NO
Is
electricity
being introduce
for the first time after
installationor after an indoor
or outdoor or BP unit
PCB has been
replaced?
Is
indoor - BP and
BP - outdoor unit
transmission wiring
normal?
YES
Normal
NO
Does a malfunction occur?
NO
Does
a "UH" malfunction occur
for all indoor units in
the system?
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to BP
and outdoor
units?
YES
Replace BP unit or indoor unit
PCB.
Replace outdoor unit PCB
(A1P).
Push and hold the RESET
button on the outdoor unit
PCB for 5 seconds
∗
The unit will not run for up to
12 minutes.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...