Outdoor Unit
Si18-525B
418
Removal Procedure
10
Disconnect the fan
motor electrical box
relay connector.
Connector X206A: Red
Connector X207A: White
5. Removing the inverter
PCB.
1
Separate the power
filter PCB mounting
plate from the electrical
assembly.
There are two hooks. Slide the
plate to unhook it.
2
Remove the reactor
connectors P1 and P2.
P1: White, P2: White
Step
Procedure
Points
(Q0486)
Hooks
(Q0487)
Inverter PCB
(Q0488)