Si18-525B
Operation Mode
Function
107
1.
Operation Mode
Operation in
stop mode
Pressure
equalization
prior to startup
Startup control
• Cooling startup
control
• Heating startup
control
Oil return IN
conditions are met.
Operation
mode change
Oil return operation
Pump-down
residual
operation
Restart standby
(Compressor stop)
Yes
Yes
No
No
Malfunction/Standby
Indoor unit stop or
thermostat OFF
Normal operation
• Compressor PI control
• Electronic expansion
valve PI control
• Protection control
Indoor unit thermostat ON
without mode change
Defrost IN
conditions are met.
No
Yes
Defrosting operation
Cooling or heating
operation
BP unit
cooling: SH control
heating: SC control
Indoor unit thermostat ON
Indoor unit stop or
thermostat OFF
Indoor unit stop or
thermostat OFF
Malfunction/
Standby
Malfunction/
Standby
Note:
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
Malfunction/Standby
(Q0372)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...