Protection Control
Si18-525B
120
Function
4.
Protection Control
4.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
In cooling operation
Pc>3.6MPa
Every 10 sec.
Pc>3.55MPa
Pc<3.45MPa
Pc>3.75MPa
Keeping the current step
Every 60 sec.
3.45MPa<Pc
≤
3.55MPa
Every
5 min.
or
&
High pressure not limited
High pressure limited
INV upper limit frequency:
1-step up from current
compressor frequency
INV upper limit frequency:
1-step up from current
compressor frequency
Pc: HP pressure sensor detection value
INV upper limit frequency :
1-step down from current
compressor frequency
When occurring 3 times within 30
minutes, HPS is activated without high
pressure standby, thus outputting the
malfunction code "E3".
High pressure
standby
(Q0374)
•
INV upper limit frequency
•
Pc
≤
3.55MPa
•
During oil return operation
•
After oil return operation
•
Stopping operation
•
Heating operation
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...