Si18-525B
Indoor Unit (SkyAir Models)
Function
149
Condensation
Avoidance
Control (FHQ
Only)
Note:
1. Regardless of thermostat ON or OFF, the control can be functioned with the operation mode
of “cooling (automatic cooling)” or “programmed drying”.
2. The function is not provided for models other than FHQ models.
Outdoor Unit
Identification
Function
If the indoor unit is for both a heat pump and cooling only type, this function differentiates
whether the outdoor unit is functioning as a heat pump or cooling only unit, and automatically
decides the which operation modes can be set.
Operation modes which can be set
Heat pump : Fan / cool / dry / auto / heat
Drain Pump Control
After continuous 30 minutes of operation with downward
horizontal blade position, change the blade position to
level, and after one hour, the unit operation can be reset.
The unit operation can be reset with changing operation
mode into "heating" , changing air flow direction or turning
"ON" or "OFF" the unit operation.
(S1117)
Continuous 30 minutes operation of cooling
One hour drying
Time A shown in below diagram
(Period from occurrence of drain water level abnormality to
compressor stop)
FHQ
10
Other than FHQ
0
1 Cooling and dry operation
1-1 Basic operation
A [sec]
Drain pump
ON
OFF
Compressor
ON
OFF
5min
For cooling or dry operation mode, drain pump is turned ON on compressor starting while turned OFF
when residual operation for 5 minutes is complete after compressor stopped.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...