Si18-525B
Indoor Unit (SkyAir Models)
Function
153
Using Conditions
for
Remote
Controller
Thermostat
Remote controller thermostat is equipped only in wired remote controller.
Even when “use remote controller thermostat” is selected in service mode, the remote controller
thermostat may not be used.
< Conditions not to use >
1. When the remote controller thermostat malfunctions.
2. When the one remote controller group control is applied.
(Excluding simultaneous ON/OFF operation)
3. When conditions relating set temperature with remote controller and suction air temperature
are out of the operating zone of remote controller thermostat shown in below diagram.
(Excluding when automatic operation mode is selected. Whenever operation is in the
automatic mode, remote controller thermostat can be used.)