Field Setting for SkyAir Indoor Unit
Si18-525B
184
Test Operation
4.2.2 Wireless Remote Controller
Note:
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual (optional hand book) for each optional accessory.
Procedure
1. When in the normal mode, push the “
” button for a minimum of four seconds,
and the FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “
” button.
3. Push the “
” button and select the FIRST CODE NO.
4. Push the “
” button and select the SECOND CODE NO.
5. Push the “
” button and the present settings are SET.
6. Push the “
” button to return to the NORMAL MODE.
4.3
Initial Setting Contents
Setting Contents
Indoor Models
Filter
Sign
Filter Sign
Estimation of
Accumulated
Operating
Hours
High Air
Outlet
Velocity
(for
Application
to Ceiling
Higher
than 2.7m)
Selection
of Air
Flow
Direction
F (4 way),
T (3 way),
W (2 way)
Air Flow
Direction
Adjust
Air Flow
Direction
Range
Setting
Long
Life
Filter
Type
Ceiling Mounted
Cassette type
600×600 (FFQ)
Ceiling Mounted
Cassette type
950×950 (FCQ)
Ceiling Mounted
Built-in type (FBQ)
Ceiling Suspended
type (FHQ)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...