Si18-525B
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
353
5.11
Malfunction of Remote Controller Thermistor
Remote
Controller
Display
CJ
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by temperature detected by remote controller thermistor.
Malfunction
Decision
Conditions
When the remote controller thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
Failure of sensor itself
Broken wire
Troubleshooting
Check No.02
Refer to P.358
Turn the power supply
off once and then
back on
Replace remote controller.
Could be outside cause
(noise,etc.) other than
malfunction
Is CJ
displayed on the
remote
controller?
NO
YES
(Q0419)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
+
See
Check No. 02
for “Thermistor temperature and resistance characteristics”.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...