Troubleshooting for SkyAir Indoor Unit
Si18-525B
354
Troubleshooting
5.12 Transmission Error (
between Indoor Unit and Remote
Controller
)
Remote
Controller
Display
U5
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Failure of remote controller
Failure of indoor PCB
Outside cause (noise, etc.)
Connection of 2 master remote controllers (When using 2 remote controllers)
Troubleshooting
Set one of the remote
controllers to"sub,"turn
off the power supply
temporarily, then restart
operation.
Indoor unit PCB
replacement
Malfunction could be
produced by noise.
Check the surrounding
area and restart
operation.
Change to double-core
independent cable.
Failure of remote
controller PCB or
replacement of
defective indoor unit
PCB
Malfunction could be
produced by noise.
Check the surrounding
area and restart
operation.
All indoor unit
PCB microcomputer
normal monitors
blinking
Control by 2
remote controllers
NO
YES
YES
YES
YES
YES
Resets
normally when power
supply is turned off
temporarily.
NO
(Q0420)
SS1 of both
remote controllers is
set to "main."
YES
NO
NO
NO
Is it good
condition from noise
interference?
Using multicore
transmission wiring
between indoor unit and
remote controller
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...