Troubleshooting for SkyAir Indoor Unit
Si18-525B
358
Troubleshooting
Check No. 02
Check for Thermistors
Disconnect the thermistor connector from PCB, then measure the resistance by using a tester.
Thermistor temperature and resistance characteristics
Unit : k
Ω
Temperature
°C
A
B
-6.0
90.8
88.0
-4.0
81.7
79.1
-2.0
73.5
71.1
0.0
66.3
64.1
2.0
59.8
57.8
4.0
54.1
52.3
6.0
48.9
47.3
8.0
44.3
42.9
10.0
40.2
38.9
12.0
36.5
35.3
14.0
33.2
32.1
16.0
30.2
29.2
18.0
27.5
26.6
20.0
25.1
24.3
22.0
23.0
22.2
24.0
21.0
20.3
26.0
19.2
18.5
28.0
17.6
17.0
30.0
16.2
15.6
32.0
14.8
4.2
34.0
13.6
13.1
36.0
12.5
12.0
38.0
11.5
11.1
40.0
10.6
10.3
42.0
9.8
9.5
44.0
9.1
8.8
46.0
8.4
8.2
48.0
7.8
7.6
50.0
7.2
7.0
52.0
6.9
6.7
54.0
6.2
6.0
56.0
5.7
5.5
58.0
5.3
5.2
Application
Heat exchanger
(Indoor/Outdoor units)
Suction air
Remote controller
Air
Outdoor air
Suction pipe
Radiator fin
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...