Si18-525B
Troubleshooting for BP Unit
Troubleshooting
361
6.3
Faulty BP Liquid or Gas Pipe Thermistor
Remote
Controller
Display
J0
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the BP liquid or gas pipe temperature sensor became short-circuited or open.
Supposed
Causes
Faulty BP liquid or gas pipe temperature sensor
Faulty connectors connection of BP liquid or gas pipe temperature sensor
Troubleshooting
Temp.
Resistance
-10°C
117k
Ω
0°C
67k
Ω
10°C
40k
Ω
20°C
25k
Ω
30°C
16k
Ω
40°C
10k
Ω
50°C
7k
Ω
60°C
5k
Ω
70°C
3k
Ω
Replace thermistor or
thermistor assembly.
If insufficient contact is not
detected, replace the
corresponding PCB.
YES
Is the resistance
normal referring to the
table below?
NO
(Q0392)
Disconnect the thermistor
connectors from the
corresponding BP PCB and
measure the resistance of
liquid or gas tube temperature
sensor.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...