Si18-525B
Troubleshooting for Outdoor Unit
Troubleshooting
379
7.14
Malfunction of Low Pressure Sensor
Remote
Controller
Display
JC
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Decision
Conditions
When the low pressure sensor is short circuit or open circuit.
Supposed
Causes
Defect of low pressure sensor
Connection of high pressure sensor with wrong connection.
Defect of outdoor unit PCB.
Troubleshooting
∗
1: Voltage measurement point
∗
2: Refer to pressure sensor, pressure/voltage characteristics table on P400.
(Q0434)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
relationship
between the
∗
1
VL and low pressure is
normal (see
∗
2) when voltage
is measured between X45A pins
(2) and (3) of outdoor unit
PCB (A1P)
(see
∗
1).
Replace the low pressure sensor.
Connect low pressure sensor
property and restart system.
NO
NO
Replace outdoor unit PCB A1P.
YES
YES
The low
pressure sensor is
connected to X45A (blue)
of outdoor unit PCB
(A1P).
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...