Troubleshooting for Outdoor Unit
Si18-525B
386
Troubleshooting
7.20
Malfunction of Inverter Radiating Fin Temperature Rise
Sensor
Remote
Controller
Display
P4
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator fin temperature sensor
Defect of inverter PCB
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P398.
(Q0440)
After resetting, restart.
YES
YES
Is the
resistance of thermistor
correct?
Is the resetting possible?
Replace inverter PCB.
Measure the resistance of
radiation fin thermistor.
NO
Replace inverter PCB.
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...