Specifications
Si18-525B
42
Specifications
1.2
Heat Pump
1.2.1 Outdoor Units
50Hz 220-230V / 60Hz 220-230V
Note:
1.
Refrigerant charge is required. (Chargeless piping length 0m)
Formula for calculation charge : R (kg)
R = Total length (m) of liquid pipe size at
φ
9.5×0.054 + Total length (m) of liquid piping size at
φ
6.4×0.022
2. The data are based on the conditions shown in the table below.
Model
RMXS112DVM
RMXS140DVM
RMXS160DVM
4HP
5HP
6HP
Cooling Capacity
kW
(kcal/h)
11.2 (9,630)
14.0 (12,040)
15.5 (13,330)
Heating Capacity
kW
(kcal/h)
12.5 (10,750)
16.0 (13,760)
17.5 (15,050)
Total Indoor Unit Capacity
kW
5.5~14.5
7.0~18.2
8.0~20.8
Power Consumption
W
—
Running Current
A
—
Casing Color
Ivory White
Compressor
Type
Hermetically Sealed Scroll Type
Model
JT100FCVD
Motor Output
(2.2kW/60rps)
kW
2.5
3.0
3.5
Refrigerant
Oil
Model
DAPHNE FVC68D
Charge
L
1.6
Refrigerant
Type
R-410A
Charge
kg
5.1
Air Flow Rate
(H)
Cooling
m³/min
(cfm)
104 (3,671)
106 (3,742)
106 (3,742)
Heating
m³/min
(cfm)
102 (3,600)
106 (3,742)
106 (3,742)
Fan
Type
Propeller
Motor Output
W
70+70
Running Current
A
0.4+0.4
Power Consumption
W
88+88
Starting Current
A
18.5-17.6-17.3
23.7-22.6-22.2
25.2-24.9-24.6
Dimensions (H×W×D)
mm
1,345×900×320
Package Dimensions (H×W×D)
mm
1,475×925×390
Weight
kg
136
Gross Weight
kg
146
Operation
Sound
Cooling
dBA
52
53
54
Heating
dBA
54
55
56
Piping
Connection
Liquid
mm
φ
9.5 (Flare Connection)
Gas
mm
φ
19.1 (Brazing Connection)
Drain
mm
φ
18
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 For Power Supply (Including Earth Wiring), 2 For Interunit Wiring (Outdoor Unit-BP)
Max. Interunit
Piping
Length
Total main piping and
branch piping
m
115
135
145
Total main piping
m
55
Total branch piping
m
60
80
90
Max. length for each
room
m
15
Necessity of Additional Charge
kg/m
Necessary
Max. Installation Height Difference
m
30 (Between Indoor or BP Unit and Outdoor Unit), 15 (Both between Indoor Units and BP Units)
Cooling
Heating
Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
Main Piping : 5m
Branch Piping : 3m
Level difference:0m
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
BP Unit
Outdoor Unit
Main Piping
Branch Piping
Indoor Unit
(Q0143)
Summary of Contents for D-Series
Page 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Page 33: ...List of Functions Si18 525B 20 List of Functions ...
Page 71: ...Specifications Si18 525B 58 Specifications ...
Page 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Page 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Page 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Page 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Page 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Page 475: ...Si18 525B vi Index ...