5 Commissioning

Installation manual

26

D035A1/4AB + D035A4AB

Wall-mounted condensing boiler

3P469346-5N – 2019.11

DANGER

Isolate  the  boiler  from  the  power  mains  before  gas
conversion operation.

INFORMATION

Only for Belgium

Gas conversion from Natural gas to propane gas can only
be  executed  by  Daikin  Belux  Service  Department.  Please
contact  Daikin  Belux  Service  Department  to  organise  an
appointment on site.

4.10.1

To convert the system for use with a
different type of gas

1

Open the front cover of the unit as described in this manual.

2

To set natural gas, adjust screw on the gas valve to position "1".

3

To set LPG, adjust the screw to position "2".

4

Mount  the  front  cover,  connect  the  unit  to  the  main  power
supply.

4.10.2

To modify settings for gas conversion

1

Enter  the  menu  section  from  the  user  interface.  Select  service
settings by using the left dial.

2

Press  the  "Enter"  button  and  choose  the  password  (742)  by
using the right dial and press the "Enter" button again.

3

Choose  "C"  parameters  via  left  dial  and  press  the  "Enter"
button.

4

Choose  "CE"  and  press  the  "Enter"  button.  It  will  ask  for
password  again.  Choose  the  password  (115)  and  press  the
"Enter" button.

5

Choose "C0" and press the "Enter" button.

6

To convert to LPG, choose "1" with the right dial and press the
"Enter"  button,  To  convert  to  Natural  gas,  choose  "0"  with  the
right dial and press the "Enter" button.

7

Leave  the  menu  screen  and  go  back  to  the  home  screen  by
using the "Back" button.

INFORMATION

When  a  conversion  is  performed,  the  identification  label
shall be marked to show the gas type in use.

5

Commissioning

WARNING

Only qualified persons should conduct commissioning.

CAUTION

Preliminary  electrical  system  checks  such  as  earth
continuity,  polarity,  resistance  to  earth  and  short  circuit
must  be  carried  out  by  using  a  suitable  test  meter  by  a
competent person.

Especially for UK:

It  is  a  requirement  that  the  boiler  is  installed  and  commissioned  to
the  manufacturer’s  instructions  and  the  data  fields  on  the
commissioning checklist completed in full.

To  instigate  the  boiler  guarantee  the  boiler  needs  to  be  registered
with the manufacturer within one month of the installation.

To  maintain  the  boiler  guarantee  it  is  essential  that  the  boiler  is
serviced annually by a Gas Safe registered engineer who has been
trained  on  the  boiler  installed.  The  service  details  should  be
recorded on Service Interval Record and left with the householder.

5.1

To fill the condensate trap

INFORMATION

Water must be poured into the 

inner

 tube.

Fill the condensate trap by pouring 0.3 litres of water from the boiler
flue outlet.

5.2

Gas-air ratio: No need to adjust

The  installer  does  not  have  to  adjust  the  gas-air  ratio,  because  the
boiler has an electronic gas adaptive feature.

5.3

To check for gas leakage

DANGER

Before passing next steps, this control must be fulfilled.

1

Before  connecting  the  unit  to  power  mains,  close  valves  1,  2
and 3.

2

Connect a manometer to gas counter.

3

Open valves 1, 2 and 3.

4

Close valve 1.

5

Note the manometer measurement and wait for 10 minutes.

6

After  10  minutes,  compare  the  manometer  measurement  with
the initial value. If the pressure is decreased, it means there is
gas leakage. Check the gas line and fittings.

7

Repeat this process until being sure that there is no leakage.

8

Close valve 1, remove the manometer and open valve 1 again.

Summary of Contents for D2CND028A1AB

Page 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND028A1AB D2CND028A4AB D2CND035A1AB D2CND035A4AB D2TND028A4AB D2TND035A4AB...

Page 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Page 3: ...pressure 29 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the vario...

Page 4: ...r 2 Safety instructions These instructions are exclusively designed for qualified competent persons Work on gas units must only be carried out by a qualified gas fitter Work on electrical equipment mu...

Page 5: ...s preventing the pressure from rising Safety valve When the water pressure of the heating circuit exceeds 3 bar some water is automatically drained from the safety valve to keep the pressure below 3 b...

Page 6: ...5A1 4AB D2TND028 035A4AB Wall mounted condensing boiler 3P469346 5N 2019 11 Bottom view of model D2CND028A4AB and D2CND035A4AB 90 65 65 68 65 37 5 125 132 180 Bottom view of models D2TND028A4AB and D2...

Page 7: ...s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling valve included in model D2CN...

Page 8: ...31 Consumption min max m h 0 2 1 09 0 2 1 38 0 2 1 09 0 2 1 38 Combustion products mass flow rate min max G20 g s 2 2 12 35 2 2 15 47 2 2 12 35 2 2 15 47 Combustion products mass flow rate min max G31...

Page 9: ...heaters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document suc...

Page 10: ...urrent I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas formation an...

Page 11: ...pressure bar In case system charge pressure needs to be more than 1 bar gas side initial charge pressure must be increased to the pressure value that is equal to system charge pressure Make sure that...

Page 12: ...g circuit 0 0 100 200 300 400 500 600 700 800 200 400 600 800 1000 1200 1400 1600 1800 A mbar B l h A Residual pump lift mbar B Flow l h 4 8 Connections NOTICE During installation do not loosen or rem...

Page 13: ...he following instructions WARNING Ignoring the rules explained below may result in serious damages in installation or boiler or cause discomfort of the user The manufacturer is not responsible for any...

Page 14: ...pacity or incomplete electrical work may cause electrical shock or fire A main switch or other means for disconnection having a contact separation in all poles providing full disconnection under overv...

Page 15: ...able glands that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG9 PG7 PG7 PG9 Holes on th...

Page 16: ...Wall mounted condensing boiler 3P469346 5N 2019 11 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND028A1AB D2CND028A...

Page 17: ...Card Ext2 X10 Personal computer production interface Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M...

Page 18: ...vent backflow from common chimney Approved ue systems Choose a flue type according to the installation site Approved flue types are written on the identification label Flue termination The positions o...

Page 19: ...nsible for atmospheric conditions when siting flue terminals CAUTION Once the flue system has been installed and the appliance commissioned the installer should observe the plume direction Particular...

Page 20: ...rom the outside and expels flue gas to the outside through a concentric coaxial pipe via the roof The terminal outlets from separate combustion and air supply circuits shall fit inside a square of 50...

Page 21: ...lowable length of the ue duct up to common chimney is 2 metres 1 60 100 90 elbow In C43x type units condensate flow into the unit is not allowed Type C63x concentric flue system INFORMATION C63 flue t...

Page 22: ...mm 1 0 m Equivalent length of options 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air...

Page 23: ...circular and rough 130 11 6 34 1 Allowable flue length for C93x DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex square and rough 130 20 6 60 6 DN 80 Fle...

Page 24: ...909 43 47 EKFGT6305 48 52 EKFGT6306 53 57 EKFGT6307 Flat roof outlet kit 60 100 EKFGP6940 80 125 EKFGW5333 Flue part Order code Wall bracket DN 100 EKFGP4631 DN 125 EKFGP4481 60 100 to 80 125 adapter...

Page 25: ...filling pressure Filling operation should be done slowly When pressure exceeds 0 8 bar error code will disappear and the status indicator light will turn to blue Turn the valve 7 off 7 You can monito...

Page 26: ...5 Commissioning WARNING Only qualified persons should conduct commissioning CAUTION Preliminary electrical system checks such as earth continuity polarity resistance to earth and short circuit must b...

Page 27: ...the sweeper mode gas analyzer device should be mounted to its place on the flue 3 To activate the sweeper mode press Cancel and Menu buttons together 5 seconds With sweeper mode boiler can be operated...

Page 28: ...s under the relevant national regulations Explain and demonstrate the lighting and shutting down procedures Explain the function and the use of the boiler heating and domestic hot water controls Expla...

Page 29: ...person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMI...

Page 30: ...g co uk It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND...

Page 31: ......

Page 32: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 5N 2019 11 Copyright 20...

Reviews: