7 Error codes

Operation manual

11

D035A1/4AB + D035A4AB
Wall-mounted condensing boiler
3P469438-5M – 2019.11

#

Problem

Solution

16-64

Flue temperature
signalise overheating

Check flue gas discharge path.

Perform reset if needed. If problem
repeats, contact your service agent.

1J-64

High limit thermostat
signalise overheating

▪ Check  the  valves  of  the  radiators

in the heating circuit.

▪ Check  the  combi  boiler  water

pressure. If it is low, fill the heating
circuit with water.

▪ Perform  reset.  If  problem  repeats,

contact your service agent.

80-01

Return temperature
sensor fault

Perform reset. If problem repeats,
contact your service agent.

81-01

Flow temperature
sensor fault

Perform reset. If problem repeats,
contact your service agent.

81-65

Domestic hot water
solar temperature
sensor fault

Boiler continues operation but solar
sensor is defective. Contact your
service agent.

8A-46

Freeze protection

Unit does not operate if flow
temperature sensor reads value less
than 1°C. Wait until the error code is
removed from the screen.

8H-64

Flow temperature
steep rise

Make sure radiator valves are open
enough to circulate water. Your
boiler will operate again after a while.
If problem repeats, contact your
service agent.

8H-65

Flow-return
temperature
difference too much

Make sure radiator valves are open
enough to circulate water. If problem
repeats, contact your service agent.

E1-64

Flame detection
before burner
operation

Perform reset. If problem repeats,
contact your service agent.

E1-65

Internal SCOT
system error

Perform reset if needed. If problem
repeats, contact your service agent.

E1-66

Calibration conditions
fault

No reset needed. Wait burner to
restart. If problem repeats, contact
your service agent.

E1-67

Missing calibration

Perform reset. If problem repeats,
contact your service agent.

E1-68

Ion base value is
outside the factory
limits or saved
incorrectly

Perform reset. If problem repeats,
contact your service agent.

E1-69

Parameter CRC error Perform reset. If problem repeats,

contact your service agent.

E1-70

Parameter CRC error Perform reset. If problem repeats,

contact your service agent.

E1-71

EK lockout failure

Permanent error. Contact your
service agent.

E1-72

SCOT flame amplifier Perform reset if needed. If problem

repeats, contact your service agent.

E1-73

Internal PCB error

Perform reset if needed. If problem
repeats, contact your service agent.

H9-01

Outside sensor fault

Boiler continues operation but
outside sensor is defective. Contact
your service agent.

HC-01

Domestic hot water
temperature sensor
fault

Boiler continues operation but you
must contact your service agent.

HJ-08

High system pressure Discharge water down to 0.8 bar.

(You can bleed the radiators.)

HJ-09

Low system pressure Increase the system pressure to

0.8 bar

#

Problem

Solution

HJ-10

Water pressure
sensor fault

Contact your service agent.

J6-01

Flow temperature
sensor overheating

(Can be a blocking
error or a lockout
error)

▪ Check  the  valves  of  the  radiators

in the heating circuit.

▪ Check  the  combi  boiler  water

pressure. If it is low, fill the heating
circuit with water.

▪ Perform reset if needed. If problem

repeats,  contact  your  service
agent.

J6-20

Return temperature
sensor overheating

(Can be a blocking
error or a lockout
error)

Perform reset if needed. If problem
repeats, contact your service agent.

J6-21

Return temperature is
higher than flow
temperature

No reset needed, burner operates
itself after a small amount of time. If
problem repeats, contact your
service agent.

JJ-64

Flue temperature
sensor fault

Perform reset. If problem repeats,
contact your service agent.

U2-01

Supply voltage is
below low limit

Contact your service agent.

U2-01

Supply voltage is
above high limit

Your boiler will continue operation
but you must contact your service
agent.

U4-65

Opentherm room
thermostat
connection is
defective

Your boiler will continue operation
but Opentherm room thermostat is
out of operation. Contact your
service agent.

U4-66

CAN-bus timeout

If problem repeats, contact your
service agent.

U4-67

Remote reset
supervision

Switch off - switch on power mains. If
problem repeats, contact your
service agent.

UA-64

Blocking during BCC
update process

Contact your service agent.

UA-65

PCB requires a BCC
update

Contact your service agent.

UA-66

BCC-ID of internal
EEPROM is
inconsistent

Contact your service agent.

UA-67

BCC is missing

Contact your service agent.

UA-68

BCC is not
compatible with PCB
(BCC-ID)

Contact your service agent.

UA-69

BCC is not
compatible with PCB
(firmware)

Contact your service agent.

UA-70

BCC update error

Contact your service agent.

UH-08

Date and time are not
set

If energy metering function is
interrupted or not started, date and
time must be set to resume. Set the
date and time from t parameters
(

"3.5.3 User settings menu"

 [

4

 9])

Summary of Contents for D2CND028A1AB

Page 1: ...Operation manual Wall mounted condensing boiler English Operation manual Wall mounted condensing boiler D2CND028A1AB D2CND028A4AB D2CND035A1AB D2CND035A4AB D2TND028A4AB D2TND035A4AB...

Page 2: ...nted gas fired condensing boiler that can supply heat to central heating systems as well as supply domestic hot water Depending on settings it is possible to use the unit solely for hot water or solel...

Page 3: ...the boiler or other parts of the system Never attempt to perform maintenance or repair yourself Call a qualified service agent CAUTION Do not use sprays solvents chlorinated cleaning agents paint and...

Page 4: ...show the home screen of the active operation mode and the related setpoint depending on the system configuration see 3 3 3 Possible operation modes 45 Status icons Meaning of icons that appear on the...

Page 5: ...mode c Summer mode d Winter mode e Full off mode 3 3 3 Possible operation modes Operation mode Description Central heating only mode Only central heating operation mode is enabled The central heating...

Page 6: ...room temperature is displayed The room temperature setpoint can be adjusted from the user interface by means of the left dial or from the Daikin room thermostat The icon is shown on the screen instead...

Page 7: ...tion the unit must be connected to the power supply and its main gas valve must be open Any damage caused by frost is not covered by the warranty Frost Protection is enabled in all modes including sta...

Page 8: ...uel energy consumption Central Heating Last month kWh Description short Unit F12 d Fuel energy consumption Central Heating Current month kWh F13 d Fuel energy consumption Central Heating Current Year...

Page 9: ...value same function that can be done via the right dial when domestic hot water mode is enabled U05 When On Off room thermostat and outdoor sensor are both connected this parameter value is the virtu...

Page 10: ...Do not let your room become too hot Decreasing the room temperature during the day saves energy Have your combi boiler s maintenance performed at least annually Provide your building with sufficient...

Page 11: ...E1 73 Internal PCB error Perform reset if needed If problem repeats contact your service agent H9 01 Outside sensor fault Boiler continues operation but outside sensor is defective Contact your servi...

Page 12: ...who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference GAS BOILER SYSTEM COMMISSIONI...

Page 13: ...It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed Service Provider SERVICE RECORD SERVICE 01 AND Where Possible AND Signat...

Page 14: ......

Page 15: ......

Page 16: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469438 5M 2019 11 Copyright 20...

Reviews: