background image

5 Commissioning

Installation Manual

21

D2CNL024A1AA
Wall-mounted condensing boiler
3P469346-12R – 2021.09

4.9

To fill the system with water

CAUTION

Water  filling  must  be  done  while  the  boiler  is  in  standby
mode.

After  all  system  connections  are  performed  with  care,  perform  the
following steps:

1

Connect  the  unit  to  the  main  power  supply.  Due  to  low
pressure,  error  code  "Err  HJ-09"  will  appear  on  the  user
interface and the status indicator light will be red.

2

Open all radiator valves.

3

Set all isolating valves to vertical (open) position.

4

Measure system water height (see 

"4.5 Central heating system

requirements"

 [

4

 10]).

5

Slowly  turn  the  filling  valve  until  pressure  reaches  a  value
around  0.8  bar  for  system  heights  up  to  6  metre.  For  longer
system 

heights, 

see 

"4.5 

Central 

heating 

system

requirements"

  [

4

  10]  to  determine  filling  pressure.  Filling

operation  should  be  done  slowly.  When  pressure  exceeds
0.8  bar,  error  code  will  disappear  and  the  status  indicator  light
will turn to blue. Turn off the filling valve.

6

System  pressure  value  can  be  monitored  from  the  user
interface.

7

Make  sure  the  automatic  air  vent  valves  located  on  the  pump
and  heat  exchanger  are  opened.  Vent  the  air  from  the
installation  with  the  manual  air  vent  screws  on  the  radiators.
Make sure screws are tightened after venting.

a

a

Filling valve

8

If  after  the  venting  the  pressure  decreases  below  0.8  bar,  refill
the system with water until the pressure reaches 0.8 bar again.

9

Check  the  central  heating  circuit  -  especially  the  couplings  of
the circuit - for leakage.

10

Isolate the unit from power mains.

5

Commissioning

WARNING

ONLY qualified persons should conduct commissioning.

CAUTION

Preliminary  electrical  system  checks  such  as  earth
continuity,  polarity,  resistance  to  earth  and  short  circuit
must  be  carried  out  by  using  a  suitable  test  meter  by  a
competent person.

5.1

To fill the condensate trap

INFORMATION

Water must be poured into the 

inner

 tube.

Fill the condensate trap by pouring 0.2 litres of water from the boiler
flue outlet.

5.2

To check for gas leakage

DANGER

Before passing next steps, this control must be fulfilled.

1

Before  connecting  the  unit  to  power  mains,  close  valves  1,  2
and 3.

2

Connect a manometer to gas counter.

3

Open valves 1, 2 and 3.

4

Close valve 1.

5

Note the manometer measurement and wait for 10 minutes.

6

After  10  minutes,  compare  the  manometer  measurement  with
the initial value. If the pressure is decreased, it means there is
gas leakage. Check the gas line and fittings.

7

Repeat this process until being sure that there is no leakage.

8

Close valve 1, remove the manometer and open valve 1 again.

1

2

3

5.3

To commission the unit

Legend - User interface:

Summary of Contents for D2CNL-A1A

Page 1: ...Installation Manual Wall mounted condensing boiler English Installation Manual Wall mounted condensing boiler D2CNL024A1AA...

Page 2: ...e atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem...

Page 3: ...re easy to separate and the plastics are marked This allows the various components to be sorted for appropriate recycling or disposal Units are marked with the following symbol This means that electri...

Page 4: ...thorised third parties Otherwise the unit warranty becomes void DANGER Isolate the boiler from the power mains before working on it WARNING Unit installation commissioning repair configuration and ser...

Page 5: ...heating circuit to avoid air traps and consequent operational problems Frost protection safety system This function protects the unit and heating installation from frost damages It is controlled by t...

Page 6: ...valve motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer l Flue gas temperature sensor m Burner hood n Ignition electro...

Page 7: ...products temp at nominal heat input C 90 CO2 Emission at nominal and minimum heat input G20 8 7 9 3 0 2 NOx Class 6 Energy related products ErP specifications Symbol Unit D2CNL024A1AA Model D2CNL024 C...

Page 8: ...ualified competent persons are allowed to open the unit Certain actions explained in this document such as gas conversion optional equipment connection require that the front cover is opened 1 Loosen...

Page 9: ...oom containing a bath or a shower then particular reference is drawn to the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake a...

Page 10: ...d related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge press...

Page 11: ...mp lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 0 0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700 800 900 100...

Page 12: ...The system must be air free to protect the boiler There are two automatic air vents on the boiler one at heat exchanger the other on the pump Ensure air is discharged completely at each water filling...

Page 13: ...nal equipment is connected to the connectors which are located on the outside of the switch box Do not open the switch box to connect optional equipment Temperature control units Connector Connectio n...

Page 14: ...2021 09 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing X1A X2 X4 X5 X1M X2M X6A X7 1 1 1 1 1 1 1 1 1 1 1 1 1 X12 X10 X11 X17 X1...

Page 15: ...7 Guidelines when connecting the condensate piping DANGER In order to prevent escape of flue gases and so poisoning the condensate trap must be mounted to its place before commissioning Condensate tra...

Page 16: ...ial to ensure that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or f...

Page 17: ...rom separate combustion and air supply circuits shall fit inside a square of 50 cm and the distance between the planes of the two orifices shall be less than 50 cm a b e c c d d f g h L i a Roof termi...

Page 18: ...ncentric flue system INFORMATION C63 flue type is not applicable to Belgium To install the boiler as a C63x option the following data must be used to determine the correct diameters and lengths of the...

Page 19: ...flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external wall and expels flue gas to a shared flue system The multi served chimney is a system t...

Page 20: ...P4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802 Tile roof outlet kit 60 100...

Page 21: ...crews on the radiators Make sure screws are tightened after venting a a Filling valve 8 If after the venting the pressure decreases below 0 8 bar refill the system with water until the pressure reache...

Page 22: ...ck the CO2 values at minimum capacity 5 Press CH to switch to maximum capacity H caption will appear on screen Check the CO2 values at maximum capacity 6 To quit sweeper mode press Reset button The CO...

Page 23: ...unction of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut off the el...

Page 24: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 12R 2021 09 Copyright 2...

Reviews: