background image

4 Installation

Installation Manual

12

D2CNL024A1AA

Wall-mounted condensing boiler

3P469346-12R – 2021.09

In case gas piping is adjacent to the wall and is to be connected to
the  gas  pipe  connection  of  the  boiler  with  an  elbow,  enough  space
for taking out the condensate trap must be left. This can be done in
two ways:

1

Elbow  must  be  placed  crosswise  so  it  will  not  block  the
condensate trap when it is being taken out.

2

Elbow must be placed 120 mm below the gas piping connection
of the boiler.

4.8.3

Guidelines when connecting the water
piping

When  connecting  the  piping  to  the  boiler,  observe  the  following
instructions:

WARNING

Ignoring  the  rules  explained  below  may  result  in  serious
damages in installation or boiler or cause discomfort of the
user.  The  manufacturer  is  NOT  responsible  for  any
damage that may occur this way.

▪ The  installation  of  the  boiler  should  be  in  compliance  with  the

applicable legislation, standards, and regulations.

▪ The materials used in the installation must be in compliance with

the applicable legislation, standards, and regulations.

▪ Heating installation piping material must not allow oxygen diffusion

according to DIN4726.

▪ The  central  heating/domestic  hot  water  installation  should  be

flushed  and  visually  inspected.  Wastes,  dust,  rubbers,  and  metal
pieces generated during the installation and mounting of the boiler
must be removed in order not to cause any damage.

▪ The central heating circuit must be able to withstand a pressure of

at least 6 bar.

▪ Cross  connection  must  be  preferred  in  the  radiators  longer  than

1.5 metres.

▪ The safety valve piping should be connected to a water outlet with

an additional hose or piping. This outlet should not be installed in
places  where  there  is  risk  of  freezing,  nor  in  the  rain  gutter,  it
should  not  end  to  dry  floor  without  available  drainage  to  avoid
damaging of floor coating like parquet.

▪ The maximum pressure in the domestic hot water circuit is 10 bar.

Inspect  the  piping  taking  this  in  to  consideration.  If  the  water
pressure  of  the  main  water  supply  is  excessive,  use  an
appropriate  pressure  reducer.  Installation  must  comply  with
EN 15502-2-2.

▪ As  the  condensing  boilers  generate  condensate,  the  condensate

trap  outlet  should  be  connected  to  an  open  drain.  Piping  and
elements of the drain line must be made of acid-resistant material
like plastics. Metals like steel or copper are not allowed.

▪ The  system  must  be  air-free  to  protect  the  boiler.  There  are  two

automatic air vents on the boiler, one at heat exchanger, the other
on  the  pump.  Ensure  air  is  discharged  completely  at  each  water
filling. Bleed the radiators if necessary.

▪ If  the  boiler  will  be  connected  to  an  old  central  heating/domestic

hot water installation, then first visually inspect the old installation.
The  installation  must  be  in  compliance  with  the  capacity  of  the
boiler  and  must  not  prevent  the  efficient  running  of  it.  Dirt  in  old
system and piping must be flushed, and filters must be inspected.

▪ If old piping material does not have oxygen barrier, then it must be

separated from the boiler circuit via a plate heat exchanger and a
second pump has to be installed for necessary circulation.

▪ If  the  pressure  reading  on  the  boiler  user  interface  is  dropping

repeatedly,  most  probably  there  is  a  leakage  in  the  installation.
Inspect the installation to repair.

4.8.4

Guidelines when connecting the electrical
wiring

DANGER

Before  working  on  the  electrical  circuit  always  isolate  the
unit from the power mains.

WARNING

ONLY  qualified  persons  are  allowed  to  make  electrical
connections on the unit. Failure to observe this warning will
void  the  warranty.  The  manufacturer  is  NOT  responsible
for any damage that may occur this way.

WARNING

Use a dedicated power circuit. NEVER use a power supply
cable shared by another unit.

The unit runs on 230 V AC 50 Hz power. A power cable is delivered
with the package. The power cable must be connected to the power
supply  by  an  electrician  and  in  accordance  with  the  applicable
legislation.

a

b

3×0.75 TTR / 230 V

H05RN

1~ 230 V

50 Hz

Cat. III

a

Safety breaker (2 A)

b

Earth leakage safety breaker

Cat. III

Overvoltage category III

▪ Electrical  work  should  be  carried  out  in  accordance  with  the

installation manual and the national electrical wiring rules or code
of practice.

▪ Insufficient  capacity  or  incomplete  electrical  work  may  cause

electrical shock or fire.

▪ A main switch or other means for disconnection, having a contact

separation  in  all  poles  providing  full  disconnection  under
overvoltage category III, shall be installed in the fixed wiring.

▪ Be sure to establish an earth. Do not earth the unit to a utility pipe,

lightning  arrester,  or  telephone  earth. 

Incomplete  earth  may

cause electrical shock and fire.

▪ While  the  electrical  connections  are  being  done,  energy  should

not  be  on  the  main  power  supply  cable  and  the  main  switch
should be closed.

▪ During  the  electrical  connections,  make  sure  that  the  cables  are

well-fixed and are connected firmly and tightly.

Summary of Contents for D2CNL-A1A

Page 1: ...Installation Manual Wall mounted condensing boiler English Installation Manual Wall mounted condensing boiler D2CNL024A1AA...

Page 2: ...e atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem...

Page 3: ...re easy to separate and the plastics are marked This allows the various components to be sorted for appropriate recycling or disposal Units are marked with the following symbol This means that electri...

Page 4: ...thorised third parties Otherwise the unit warranty becomes void DANGER Isolate the boiler from the power mains before working on it WARNING Unit installation commissioning repair configuration and ser...

Page 5: ...heating circuit to avoid air traps and consequent operational problems Frost protection safety system This function protects the unit and heating installation from frost damages It is controlled by t...

Page 6: ...valve motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer l Flue gas temperature sensor m Burner hood n Ignition electro...

Page 7: ...products temp at nominal heat input C 90 CO2 Emission at nominal and minimum heat input G20 8 7 9 3 0 2 NOx Class 6 Energy related products ErP specifications Symbol Unit D2CNL024A1AA Model D2CNL024 C...

Page 8: ...ualified competent persons are allowed to open the unit Certain actions explained in this document such as gas conversion optional equipment connection require that the front cover is opened 1 Loosen...

Page 9: ...oom containing a bath or a shower then particular reference is drawn to the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake a...

Page 10: ...d related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge press...

Page 11: ...mp lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 0 0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700 800 900 100...

Page 12: ...The system must be air free to protect the boiler There are two automatic air vents on the boiler one at heat exchanger the other on the pump Ensure air is discharged completely at each water filling...

Page 13: ...nal equipment is connected to the connectors which are located on the outside of the switch box Do not open the switch box to connect optional equipment Temperature control units Connector Connectio n...

Page 14: ...2021 09 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing X1A X2 X4 X5 X1M X2M X6A X7 1 1 1 1 1 1 1 1 1 1 1 1 1 X12 X10 X11 X17 X1...

Page 15: ...7 Guidelines when connecting the condensate piping DANGER In order to prevent escape of flue gases and so poisoning the condensate trap must be mounted to its place before commissioning Condensate tra...

Page 16: ...ial to ensure that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or f...

Page 17: ...rom separate combustion and air supply circuits shall fit inside a square of 50 cm and the distance between the planes of the two orifices shall be less than 50 cm a b e c c d d f g h L i a Roof termi...

Page 18: ...ncentric flue system INFORMATION C63 flue type is not applicable to Belgium To install the boiler as a C63x option the following data must be used to determine the correct diameters and lengths of the...

Page 19: ...flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external wall and expels flue gas to a shared flue system The multi served chimney is a system t...

Page 20: ...P4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802 Tile roof outlet kit 60 100...

Page 21: ...crews on the radiators Make sure screws are tightened after venting a a Filling valve 8 If after the venting the pressure decreases below 0 8 bar refill the system with water until the pressure reache...

Page 22: ...ck the CO2 values at minimum capacity 5 Press CH to switch to maximum capacity H caption will appear on screen Check the CO2 values at maximum capacity 6 To quit sweeper mode press Reset button The CO...

Page 23: ...unction of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut off the el...

Page 24: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 12R 2021 09 Copyright 2...

Reviews: