6 Hand-over to the user
Installation manual
26
D035A1/4AA + D035A4AA
Wall-mounted condensing boiler
3P469346-5E – 2017.06
5.3
To check for gas leakage
DANGER
Before passing next steps, this control must be fulfilled.
1
Before connecting the unit to power mains, close valves 1, 2
and 3.
2
Connect a manometer to gas counter.
3
Open valves 1, 2 and 3.
4
Close valve 1.
5
Note the manometer measurement and wait for 10 minutes.
6
After 10 minutes, compare the manometer measurement with
the initial value. If the pressure is decreased, it means there is
gas leakage. Check the gas line and fittings.
7
Repeat this process until being sure that there is no leakage.
8
Close valve 1, remove the manometer and open valve 1 again.
1
2
3
5.4
To commission the unit
Legend - User interface:
a
e
f
g
c
b
d
a
Left dial
b
LCD screen
c
Right dial
d
Mode / Reset
e
Status indicator
f
Cancel / Back
g
Menu / Enter
1
Make sure the system is filled with water and fully vented as
described in this manual.
2
Check that the central heating and domestic hot water isolating
valves are open.
3
Check that gas service valve is open.
4
Connect the unit to the main power supply. The user interface
will be energised.
5.4.1
To commission the central heating
1
Set mode to winter mode via "Mode" button on the user
interface. ( and icons are displayed on the screen.)
2
Set central heating set temperature to maximum value via left
dial. If connected, make sure all external controls such as
outdoor sensor and room thermostat are calling for heat.
3
The boiler control now go through its ignition sequence. The
status indicator will glow constantly in blue if flame is
established. icon will blink when central heating is active.
INFORMATION
After first power ON, the boiler does not increase its
capacity above a preset value for about 12 minutes, even if
there is demand.
▪ First 0~2 minutes: The electronic gas adaptive system
calibrates itself.
▪ Next 8~10 minutes: The boiler performs the low water
temperature function. You can skip this function by
pressing the "Cancel" button for 5 seconds.
4
Press "Cancel" and "Menu" buttons together 5 seconds to
activate the sweeper mode. With sweeper mode, boiler can be
operated at maximum and minimum capacity independent of
heat demand.
5
"tst - 100" caption will appear on the screen. This means boiler
is operating at nominal capacity. Check nominal capacity
operation.
6
To quit sweeper mode, again press "Cancel" and "Menu"
buttons together five seconds. Sweeper mode will be
deactivated and boiler will return to normal operation mode.
Sweeper mode also finishes automatically after 15 minutes.
5.4.2
To commission the central heating
capacity setting
The boiler's central heating capacity can be adjusted form the
control panel. If the heat loss of installation is much less than that of
the boiler nominal capacity, it is recommended to reduce the boiler
nominal capacity to the installation capacity. Refer to service
instructions for this operation.
5.4.3
To commission the domestic hot water
(Only for models D2CND028 and D2CND035 )
1
Set domestic hot water set temperature to its maximum value
via right dial.
2
Open hot water taps fully and ensure that water flows freely
from them.
3
icon will blink when domestic water heating is active.
4
Measure the domestic hot water inlet temperature. (Cold water
drawn off from taps)
5
Check that domestic hot water temperature rise is around 34°C.
6
Hand-over to the user
After completing the installation and commissioning of the system
the installer should hand over to the householder.
▪ Hand the operation manual to the householder and inform them
about his/her responsibilities under the relevant national
regulations.
▪ Explain and demonstrate the lighting and shutting down
procedures.
▪ Explain the function and the use of the boiler heating and
domestic hot water controls.