background image

4 Installation

Installation manual

13

D035A1/4AA + D035A4AA
Wall-mounted condensing boiler
3P469346-5E – 2017.06

A

a

B

F

D

E

Valve

Strainer
Tee connection

Double check valve + filling hose
Disconnector

a

External filling group used with models D2TND028A4AA
and D2TND035A4AA. Use a disconnector or a double
check valve according to local regulations.

Isolation  valves  and  strainers  should  be  used  just  before  the
appliance  piping  inlet  as  shown  in  figure  above.  Boiler  is  filled  with
external fresh water supply.

Ensure that necessary gaskets are placed.

Note: 

Optional  Daikin  connection  kit  can  be  used  and  it  is

recommended to use it.

4.8.2

Guidelines when connecting the gas
piping

This  unit  is  designed  to  be  operated  with  natural  gas  or  LPG.  The
preset gas type and the designated gas inlet pressure are indicated
on the boiler's identification label.

WARNING

Only  qualified  persons  are  allowed  to  connect  the  gas
piping.  The  gas  inlet  pipe  diameter  must  be  selected
according  to  the  applicable  legislation,  standards,  and
regulations.

Connect  the  gas  piping  according  to  applicable  legislation  of  the
country  of  destination  and  the  regulations  of  the  gas  supply
company.

Connect  the  gas  supply  piping  without  tension  to  the  gas  pipe
connection  ("Connection  F",  see 

"4.8.1  Piping  connections"  on

page 12

).

WARNING

After  the  gas  connection  is  made,  the  gas  line  must  be
tested  for  leakage  while  the  gas  line  to  the  boiler  is  open
(see 

"5.3 To check for gas leakage" on page 26

).

In case gas piping is adjacent to the wall and is to be connected to
the  gas  pipe  connection  of  the  boiler  with  an  elbow,  enough  space
for taking out the condensate trap must be left. This can be done in
two ways:

1

Elbow  must  be  placed  crosswise  so  it  will  not  block  the
condensate trap when it is being taken out.

2

Elbow must be placed 200 mm below the gas piping connection
of the boiler.

4.8.3

Guidelines when connecting the water
piping

When  connecting  the  piping  to  the  boiler,  observe  the  following
instructions:

WARNING

Ignoring  the  rules  explained  below  may  result  in  serious
damages in installation or boiler or cause discomfort of the
user. The manufacturer is not responsible for any damage
that may occur this way.

▪ The  installation  of  the  boiler  should  be  in  compliance  with  the

applicable legislation, standards, and regulations.

▪ The materials used in the installation must be in compliance with

the applicable legislation, standards, and regulations.

▪ Heating installation piping material must not allow oxygen diffusion

according to DIN4726.

▪ The  central  heating/domestic  hot  water  installation  should  be

flushed  and  visually  inspected.  Wastes,  dust,  rubbers,  and  metal
pieces generated during the installation and mounting of the boiler
must be removed in order not to cause any damage.

▪ The central heating circuit must be able to withstand a pressure of

at least 6 bar.

▪ Cross  connection  must  be  preferred  in  the  radiators  longer  than

1.5 metres.

▪ The safety valve piping should be connected to a water outlet with

an additional hose or piping. This outlet should not be installed in
places  where  there  is  risk  of  freezing,  nor  in  the  rain  gutter,  it
should  not  end  to  dry  floor  without  available  drainage  to  avoid
damaging of floor coating like parquet.

▪ The maximum pressure in the domestic hot water circuit is 10 bar.

Inspect  the  piping  taking  this  in  to  consideration.  If  the  water
pressure  of  the  main  water  supply  is  excessive,  use  an
appropriate  pressure  reducer.  Installation  must  comply  with
EN 15502-2-2.

▪ As  the  condensing  boilers  generate  condensate,  the  condensate

trap  outlet  should  be  connected  to  an  open  drain.  Piping  and
elements of the drain line must be made of acid-resistant material
like plastics. Metals like steel or copper are not allowed.

▪ The  system  must  be  air-free  to  protect  the  boiler.  There  are  two

automatic air vents on the boiler, one at heat exchanger, the other
on  the  pump.  Ensure  air  is  discharged  completely  at  each  water
filling. Bleed the radiators if necessary.

▪ If  the  boiler  will  be  connected  to  an  old  central  heating/domestic

hot water installation, then first visually inspect the old installation.
The  installation  must  be  in  compliance  with  the  capacity  of  the
boiler  and  must  not  prevent  the  efficient  running  of  it.  Dirt  in  old
system and piping must be flushed, and filters must be inspected.

Summary of Contents for D2TND028A4AA

Page 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND028A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA...

Page 2: ...tatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumie...

Page 3: ...must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for...

Page 4: ...ce must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user and his her surroundings The manufacturer i...

Page 5: ...allation from frost damages It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperatu...

Page 6: ...he unit Installation manual 6 D2CND028 035A1 4AA D2TND028 035A4AA Wall mounted condensing boiler 3P469346 5E 2017 06 Bottom view of models D2TND028A4AA and D2TND035A4AA 90 30 100 103 30 125 7 72 132 1...

Page 7: ...s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling valve included in model D2CN...

Page 8: ...19 0 59 3 32 0 59 4 19 LPG G31 Consumption min max m h 0 2 1 09 0 2 1 38 0 2 1 09 0 2 1 38 Combustion products mass flow rate min max G20 g s 2 2 12 35 2 2 15 47 2 2 12 35 2 2 15 47 Combustion produc...

Page 9: ...oilers 37 C and for other heaters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions expl...

Page 10: ...o the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas forma...

Page 11: ...13 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the...

Page 12: ...1 Piping connections Piping connections of models D2CND028A1AA D2CND028A4AA D2CND035A1AA and D2CND035A4AA Below find the piping connections of the unit A B D E H C F G A Central heating return connec...

Page 13: ...ious damages in installation or boiler or cause discomfort of the user The manufacturer is not responsible for any damage that may occur this way The installation of the boiler should be in compliance...

Page 14: ...or fire A main switch or other means for disconnection having a contact separation in all poles providing full disconnection under overvoltage category III shall be installed in the fixed wiring Be s...

Page 15: ...9346 5E 2017 06 PG9 PG7 PG7 PG9 Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be used Note Un...

Page 16: ...Wall mounted condensing boiler 3P469346 5E 2017 06 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND028A1AA D2CND028A...

Page 17: ...ip Card Ext2 X10 Personal computer production interface Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal stri...

Page 18: ...lations The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue te...

Page 19: ...length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a 50 mm Note Flue ducts are inserted 45 mm into elbows...

Page 20: ...Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Tee 60 100 with measurement point h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Maximum allowable length of the ue duct up to commo...

Page 21: ...mm 1 0 m Equivalent length of options 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air...

Page 22: ...cular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Page 23: ...100 EKFGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKF...

Page 24: ...disconnector or a double check valve according to local regulations After all system connections are performed with care perform the following steps 1 Connect the appliance to the main power supply Du...

Page 25: ...ount the front cover connect the unit to the main power supply 4 10 2 To modify settings for gas conversion 1 Enter the menu section from the user interface Select service settings by using the left d...

Page 26: ...nutes even if there is demand First 0 2 minutes The electronic gas adaptive system calibrates itself Next 8 10 minutes The boiler performs the low water temperature function You can skip this function...

Page 27: ...plain the function of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut...

Page 28: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 5E 2017 06...

Reviews: