3 About the unit

Installation manual

5

D035A1/4AA + D035A4AA
Wall-mounted condensing boiler
3P469346-5E – 2017.06

Pump  anti-blockage  system

:  The  pump  operates  for  30  seconds

every 24 hours during long periods of inactivity to ensure it does not
get stuck. To enable this function, the unit must be connected to the
power supply.

Three-way valve anti-blockage system

: In cases where the unit is

non-operational  for  prolonged  periods  of  time,  the  three-way  valve
switches its position every 24 hours to prevent it from getting stuck.
To  enable  this  function,  the  unit  must  be  connected  to  the  power
supply.

Safety  against  dry  operation

:  This  is  controlled  by  the  pressure

sensor.  It  turns  off  the  unit  and  ensures  system  safety  when  the
water pressure of the heating installation falls below 0.6 bar for any
reason.

Flame  ionisation  control

:  This  is  controlled  by  the  ionisation

electrode. It checks whether a flame forms on the burner surface or
not.  If  there  is  no  flame,  it  turns  the  unit  off  to  stop  gas  flow  and
warns the user.

High pressure protection

:

Pressure  sensor

:  When  heating  system  pressure  reaches

2.8  bar,  control  unit  stops  heating  operation  thus  preventing  the
pressure from rising.

Safety  valve

:  When  the  water  pressure  of  the  heating  circuit

exceeds  3  bar,  some  water  is  automatically  drained  from  the
safety valve to keep the pressure below 3 bar thus protecting the
boiler and heating installation.

Automatic  air  vents

:  There  are  two  air  vents;  one  on  the  pump,

other on the heat exchanger. They help discharging the air inside the
installation  and  heating  circuit  to  avoid  air  traps  and  consequent
operational problems.

Frost protection safety system

: This function protects the unit and

heating  installation  from  frost  damages.  It  is  controlled  by  the  flow
temperature  sensor,  which  is  located  at  the  outlet  of  the  main  heat
exchanger. This protection activates the boiler pump when the water
temperature drops below 13°C and it activates the burner when the
water temperature drops below 8°C. The unit keeps running until the
temperature reaches 20°C. To enable this function, the unit must be
connected to the power supply and its main gas valve must be open.
Any damage caused by frost is not covered by the warranty.

Low  voltage  safety  system

:  This  is  controlled  by  the  control  unit.

When  the  supply  voltage  drops  below  170  Volt,  the  boiler  goes  to
error  mode.  It  is  a  blocking  error  and  the  boiler  will  operate  without
reset  after  supply  voltage  is  above  180  Volt.  It  is  recommended  to
use a voltage regulator of suitable power and type in locations with
voltage fluctuations below this limit for faultless operation.

High  electric  supply  current  protection  system

:  A  fuse  on  the

control  unit  protects  equipment  and  wiring  against  the  damaging
effects  of  electrical  faults  which  is  caused  by  excess  currents,  and
disables  equipment  which  is  faulty.  The  fuse  "blows"  (opens)  when
the current carried exceeds the rated value for an excessive time.

Automatic  by-pass  system

:  This  ensures  that  the  flow  is  at  all

times  continued,  to  avoid  overheating  of  the  heat  exchanger.  This
system  is  also  supported  with  a  special  by-pass  function  in  the
control unit software.

Combustion control safety system

: Boiler control unit monitors the

flame  to  avoid  bad  combustion  and  risky  conditions.  It  also  makes
self-inspection against its own malfunctioning and to keep emissions
always at a low level.

3.2

Dimensions

Top view

Front view and right side view

784.5

695.5

294.4

Bottom view of model D2CND028A1AA and D2CND035A1AA

90

65

65

68

65

37.5

12

5

13

2

18

0

Bottom view of model D2CND028A4AA and D2CND035A4AA

90

65

65

68

65

37.5

12

5

13

2

18

0

Summary of Contents for D2TND028A4AA

Page 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND028A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA...

Page 2: ...tatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumie...

Page 3: ...must be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for...

Page 4: ...ce must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user and his her surroundings The manufacturer i...

Page 5: ...allation from frost damages It is controlled by the flow temperature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperatu...

Page 6: ...he unit Installation manual 6 D2CND028 035A1 4AA D2TND028 035A4AA Wall mounted condensing boiler 3P469346 5E 2017 06 Bottom view of models D2TND028A4AA and D2TND035A4AA 90 30 100 103 30 125 7 72 132 1...

Page 7: ...s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling valve included in model D2CN...

Page 8: ...19 0 59 3 32 0 59 4 19 LPG G31 Consumption min max m h 0 2 1 09 0 2 1 38 0 2 1 09 0 2 1 38 Combustion products mass flow rate min max G20 g s 2 2 12 35 2 2 15 47 2 2 12 35 2 2 15 47 Combustion produc...

Page 9: ...oilers 37 C and for other heaters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions expl...

Page 10: ...o the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas forma...

Page 11: ...13 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the...

Page 12: ...1 Piping connections Piping connections of models D2CND028A1AA D2CND028A4AA D2CND035A1AA and D2CND035A4AA Below find the piping connections of the unit A B D E H C F G A Central heating return connec...

Page 13: ...ious damages in installation or boiler or cause discomfort of the user The manufacturer is not responsible for any damage that may occur this way The installation of the boiler should be in compliance...

Page 14: ...or fire A main switch or other means for disconnection having a contact separation in all poles providing full disconnection under overvoltage category III shall be installed in the fixed wiring Be s...

Page 15: ...9346 5E 2017 06 PG9 PG7 PG7 PG9 Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be used Note Un...

Page 16: ...Wall mounted condensing boiler 3P469346 5E 2017 06 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND028A1AA D2CND028A...

Page 17: ...ip Card Ext2 X10 Personal computer production interface Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal stri...

Page 18: ...lations The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue te...

Page 19: ...length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a 50 mm Note Flue ducts are inserted 45 mm into elbows...

Page 20: ...Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Tee 60 100 with measurement point h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Maximum allowable length of the ue duct up to commo...

Page 21: ...mm 1 0 m Equivalent length of options 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air...

Page 22: ...cular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Page 23: ...100 EKFGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKF...

Page 24: ...disconnector or a double check valve according to local regulations After all system connections are performed with care perform the following steps 1 Connect the appliance to the main power supply Du...

Page 25: ...ount the front cover connect the unit to the main power supply 4 10 2 To modify settings for gas conversion 1 Enter the menu section from the user interface Select service settings by using the left d...

Page 26: ...nutes even if there is demand First 0 2 minutes The electronic gas adaptive system calibrates itself Next 8 10 minutes The boiler performs the low water temperature function You can skip this function...

Page 27: ...plain the function of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut...

Page 28: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 5E 2017 06...

Reviews: