background image

20

APPENDIX A BLOWER PERFORMANCE DATA  

8.5 TON AC

DBC102*V STANDARD STATIC HORIZONTAL 

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

0.1

4111

732

1.42

3866

692

1.27

3636

652

1.11

3403

613

0.95

3165

600

0.74

0.2

4022

732

1.38

3784

692

1.23

3532

652

1.06

3193

613

0.87

2907

600

0.66

0.3

4176

770

1.66

3901

732

1.32

3654

692

1.17

3373

652

0.99

2983

613

0.78

2650

600

0.58

0.4

4033

770

1.57

3748

732

1.24

3477

692

1.09

3161

652

0.90

2773

613

0.71

0.5

3867

770

1.48

3563

732

1.16

3251

692

0.99

2893

652

0.80

2563

613

0.63

0.6

3678

770

1.37

3345

732

1.06

2977

692

0.88

2572

652

0.68

0.7

3465

770

1.26

3096

732

0.95

2656

692

0.76

0.8

3228

770

1.14

2815

732

0.84

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

DBC102*S HIGH STATIC HORIZONTAL

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

0.8

3894

888

1.94

3444

838

1.26

0.9

4126

940

2.15

3678

889

1.80

3228

840

1.16

1.0

3922

942

2.01

3434

891

1.65

2984

842

1.04

1.1

4194

987

2.42

3702

943

1.86

3162

895

1.49

2712

845

0.92

1.2

3990

990

2.26

3467

944

1.71

2862

899

1.32

1.3

4245

1044

2.52

3773

993

2.10

3216

945

1.56

2534

905

1.15

1.4

4004

1047

2.33

3542

996

1.94

2950

946

1.41

1.5

3737

1050

2.14

3297

1000

1.77

2668

947

1.26

1.6

4139

1096

2.66

3444

1053

1.93

3039

1003

1.61

1.7

3939

1093

2.49

3125

1050

1.72

2767

1000

1.44

1.8

3732

1096

2.32

2781

1053

1.51

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

1

To operate below 0.8" H

2

O external static pressure, motor and blower sheave must be changed to VL40 and AK84H respectively, or equivalents

DBC102*V STANDARD STATIC DOWNSHOT

1

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

0.1

3988

613

1.05

3681

600

0.93

0.2

4070

652

1.31

3708

613

0.94

3349

600

0.81

0.3

4160

692

1.42

3773

652

1.17

3391

613

0.83

2986

600

0.69

0.4

4269

732

1.50

3882

692

1.28

3455

652

1.02

3037

613

0.71

2593

600

0.57

0.5

4004

732

1.37

3574

692

1.13

3116

652

0.88

2645

613

0.59

0.6

4106

770

1.61

3715

732

1.23

3236

692

0.98

2757

652

0.74

0.7

3836

770

1.46

3403

732

1.08

2867

692

0.83

0.8

3550

770

1.30

3068

732

0.94

2

3

4

5

ESP, In H

2

O

TURNS OPEN

0

1

DBC102*S HIGH STATIC DOWNSHOT

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

CFM

RPM

BHP

0.8

4197

1076

2.15

3676

1077

1.38

0.9

3991

1077

2.00

3391

1078

1.23

1.0

4141

1077

2.15

3708

1078

1.82

3017

1079

1.05

1.1

3871

1078

1.97

3347

1079

1.59

2556

1080

0.85

1.2

4170

1078

2.40

3586

1079

1.78

2908

1080

1.34

1.3

3871

1079

2.17

3287

1080

1.60

1.4

4193

1079

2.47

3539

1080

1.93

2973

1081

1.42

1.5

3946

1080

2.28

3175

1081

1.69

2645

1082

1.24

1.6

4235

1080

2.56

3690

1081

2.09

2777

1082

1.44

1.7

3995

1081

2.37

3426

1082

1.90

1.8

3745

1082

2.19

3152

1083

1.72

1

To operate below 0.8" H

2

O external static pressure, motor and blower sheave must be changed to VL40 and AK84H respectively, or equivalents

ESP, In H

2

O

TURNS OPEN

0

1

2

3

4

5

Summary of Contents for DBC Series

Page 1: ...erty damage arising from improper service or service procedures If you service this unit you assume responsibility for any injury or property damage which may result In addition in jurisdictions that...

Page 2: ...B Electrical Data 27 Appendix C Unit Dimensions 40 Appendix D Min Max Airflow 41 Wiring Diagram 42 Start Up Checklist 44 To The Installer Before installing this unit please read this manual to familia...

Page 3: ...cepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation The mechanical installation of the package...

Page 4: ...tly on wood floors or on Class A Class B or Class C roof covering material To avoid possible personal injury a safe flat surface for service personnel should be provided As indicated on the unit data...

Page 5: ...rk must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perimeter curbs include duct connection frames to be assemble...

Page 6: ...nit base frame from fork lift damage Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit Refer to rigging label on the unit Your unit ma...

Page 7: ...65 302 Corner Weight B 359 347 344 401 Corner Weight C 267 300 317 312 Corner Weight D 302 311 290 379 Unit Shipping Weight 1227 1287 1291 1394 Unit Operating Weight 1152 1212 1216 1314 X inches 43 44...

Page 8: ...ree wire The unit is factory wired for the voltage shown on the unit s data plate NOTE If supply voltage is 208V lead on primary of transformer s must be moved from the 230V to the 208V tap Refer to w...

Page 9: ...holes in the unit base must be sealed including those around conduit nuts to prevent water leakage into building All required conduit and fittings are to be field supplied Supply voltage to roof top...

Page 10: ...connection is supplied on the end of the unit and bottom of the drain pan for condensate piping An external trap must be installed for proper condensate drainage Hand tighten drain fitting to the drai...

Page 11: ...installation instructions All electric power all gas hot water or steam line connections and the condensate drain installation have been made to each unit on the job These main supply lines must be f...

Page 12: ...run high stage CFM below 300 CFM per ton evaporator freezing or poor unit performance is possible Evaporator Fan Rotation Check Check that fan rotates clockwise when viewed from the drive side of unit...

Page 13: ...GROOVES 5 Ensure all keys are in place and the set screws tight before starting drive Recheck set screws and belt tension after 24 hours service NOTE Future adjustments should be made by loosening th...

Page 14: ...ly checked so postpone the test to another day when conditions are more suitable but DO NOT FAIL TO TEST If the outdoor ambient is low and the unit operates properly on the heating cycle you may check...

Page 15: ...dels with V or S in the 8th position of the model number For 2 speed models the indoor blower will operate on low speed when in Fan Only mode or while in first stage Cooling mode Unit will operate on...

Page 16: ...also act as check valves to allow for the reverse of refrigerant flow When the heat pump is on the heating cycle the outdoor coil is functioning as an evaporator The temperature of the refrigerant in...

Page 17: ...rently have sharp edges and it is necessary that the installer and service personnel exercise caution Preventive maintenance is the best way to avoid unnecessary expense and inconvenience Have this sy...

Page 18: ...allow air entering the indoor coil to drop below 65 F Air below this temperature will cause low discharge pressure thus low suction pressure and excessive defrost cycling resulting in low heating outp...

Page 19: ...1 51 2481 1003 1 28 DBC090 S HIGH STATIC HORIZONTAL1 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK84H re...

Page 20: ...44 1 8 3732 1096 2 32 2781 1053 1 51 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK84H respectively or eq...

Page 21: ...O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VL40 and AK74H respectively or equivalents DBC120 V STANDARD STATIC DOWNSHOT1 CF...

Page 22: ...5348 1144 4 26 4928 1106 3 77 4389 1068 3 19 3762 1030 2 22 ESP In H2O TURNS OPEN 0 1 2 3 4 5 1 To operate below 0 8 H2O external static pressure motor and blower sheave must be changed to VP44 and AK...

Page 23: ...P CFM RPM BHP CFM RPM BHP 0 1 3532 620 1 05 3276 600 0 78 0 2 3601 663 1 13 3264 620 0 93 2947 600 0 67 0 3 3654 707 1 18 3323 663 1 00 2955 620 0 81 2617 600 0 57 0 4 3728 748 1 24 3377 707 1 05 3011...

Page 24: ...2 83 2797 1058 2 10 DBH102 V STANDARD STATIC DOWNSHOT1 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 3933 610 1 29 0 2 4039 655 1 46 3658 611 1 20 0 3 4172 693 1 66 3763...

Page 25: ...DOWNSHOT1 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0 1 4836 649 1 73 4463 610 1 41 0 2 4976 692 1 97 4557 650 1 60 4177 610 1 30 0 3 4641 693 1 82 4213 653 1 47 3783 61...

Page 26: ...2 5963 762 2 57 5529 721 2 24 5102 681 1 69 4625 642 1 43 0 3 5716 762 2 40 5241 721 2 06 4778 681 1 53 4276 642 1 27 0 4 5439 762 2 22 4929 721 1 87 4429 681 1 36 3910 642 1 12 0 5 5581 805 2 90 5131...

Page 27: ...24 30 1 20 7 25 4 3 1 25 30 27 9 30 4 3 33 3 35 1 29 2 30 4 3 1 34 6 35 50 5 60 4 3 55 9 60 1 51 7 60 4 3 1 57 1 60 73 80 4 3 78 4 80 1 74 3 80 4 3 1 79 7 80 18 3 20 4 3 22 6 25 1 19 3 20 4 3 1 23 6...

Page 28: ...0 45 9 45 6 50 50 9 6 8 7 3 3 3 0 55 5 54 3 60 60 46 6 52 6 50 60 9 6 8 7 58 6 63 5 60 70 3 3 3 0 50 7 56 4 60 60 9 6 8 7 3 3 3 0 62 7 67 2 70 70 85 7 97 7 90 100 9 6 8 7 97 7 109 100 110 3 3 3 0 89 8...

Page 29: ...25 1 2 18 5 20 3 5 1 2 22 25 21 25 3 5 25 4 30 1 2 22 5 25 3 5 1 2 26 9 30 39 1 40 3 5 43 5 45 1 2 40 6 45 3 5 1 2 45 45 57 1 60 3 5 61 5 70 1 2 58 6 60 3 5 1 2 63 70 Model Number Electrical Rating C...

Page 30: ...35 1 24 5 30 4 3 1 28 8 35 27 9 30 4 3 33 3 35 1 29 2 30 4 3 1 34 6 35 50 5 60 4 3 55 9 60 1 51 7 60 4 3 1 57 1 60 73 80 4 3 78 4 80 1 74 3 80 4 3 1 79 7 80 22 1 25 4 3 26 4 30 1 23 1 25 4 3 1 27 4 30...

Page 31: ...60 6 60 3 70 70 9 6 8 7 3 3 3 0 70 2 69 0 80 80 57 3 57 3 70 70 9 6 8 7 66 9 67 4 80 80 3 3 3 0 60 6 60 3 70 70 9 6 8 7 3 3 3 0 70 2 71 1 80 80 89 6 102 90 110 9 6 8 7 102 112 110 125 3 3 3 0 93 7 10...

Page 32: ...1 2 23 4 25 3 5 1 2 26 9 30 22 4 25 3 5 26 8 30 1 2 23 9 25 3 5 1 2 28 3 30 40 5 45 3 5 44 8 45 1 2 42 45 3 5 1 2 46 3 50 58 5 60 3 5 62 9 70 1 2 60 70 3 5 1 2 64 4 70 Model Number Electrical Rating...

Page 33: ...22 2 25 4 3 1 26 5 30 43 8 45 4 3 48 1 50 1 44 8 45 4 3 1 49 1 50 66 3 70 4 3 70 6 80 1 67 3 70 4 3 1 71 6 80 88 9 90 4 3 93 2 100 1 89 9 90 4 3 1 94 2 100 19 8 25 4 3 24 1 30 1 20 8 25 4 3 1 25 1 30...

Page 34: ...0 48 9 48 6 60 60 9 6 8 7 3 3 3 0 58 5 57 3 60 60 84 7 90 7 90 100 9 6 8 7 94 3 99 4 100 100 3 3 3 0 88 0 93 7 90 100 9 6 8 7 3 3 3 0 97 6 102 100 110 124 136 125 150 9 6 8 7 133 145 150 150 3 3 3 0...

Page 35: ...26 5 30 1 2 24 2 25 3 5 1 2 27 7 30 41 45 3 5 44 5 45 1 2 42 2 45 3 5 1 2 45 7 50 59 60 3 5 62 5 70 1 2 60 2 70 3 5 1 2 63 7 70 77 1 80 3 5 80 6 90 1 2 78 3 80 3 5 1 2 81 8 90 Model Number Electrical...

Page 36: ...1 24 4 30 4 3 1 28 7 30 45 9 50 4 3 50 2 60 1 46 9 50 4 3 1 51 2 60 68 5 70 4 3 72 8 80 1 69 5 70 4 3 1 73 8 80 91 100 4 3 95 3 100 1 92 100 4 3 1 96 3 100 22 25 4 3 26 3 30 1 23 25 4 3 1 27 3 30 44...

Page 37: ...3 5 60 5 70 1 2 58 2 60 3 5 1 2 61 7 70 75 1 80 3 5 78 6 80 1 2 76 3 80 3 5 1 2 79 8 80 EH B 7M46 45 43 3 DBH1207S 575 3 60 2 5 1 39 5 2 0 33 3 5 2 speed Belt Drive High Static 3 3 5 EH B 7M16 15 14...

Page 38: ...5 9 6 8 7 3 3 3 0 156 167 175 175 182 200 200 225 9 6 8 7 192 209 200 225 3 3 3 0 186 203 200 225 9 6 8 7 3 3 3 0 195 212 200 225 33 2 40 4 3 37 5 45 1 34 2 40 4 3 1 38 5 45 55 7 60 4 3 60 70 1 56 7 6...

Page 39: ...30 40 8 45 3 5 44 3 45 1 2 42 45 3 5 1 2 45 5 50 58 9 60 3 5 62 4 70 1 2 60 1 70 3 5 1 2 63 6 70 76 9 80 3 5 80 4 90 1 2 78 1 80 3 5 1 2 81 6 90 Optional Powered Convienience Optional Power Exhaust Po...

Page 40: ...d on the flanges around the duct openings and the gasket is APPENDIX C UNIT DIMENSIONS Horizontal Discharge Vertical Discharge Bottom of Unit NOTE For horizontal discharge remove supply and return duc...

Page 41: ...903S 2400 X X X X X X DBC0904S 2400 X X X X X X DBC0907S 2400 X X X X X X DBC1023S 2750 X X X X X X DBC1024S 2750 X X X X X X DBC1027S 2750 X X X X X X DBC1203S 3250 X X X X X X DBC1204S 3250 X X X X...

Page 42: ...ITH PINK STRIPE BR BROWN GR GREEN GY GRAY OR ORANGE PK PINK PU PURPLE RD RED TN TAN WH WHITE YL YELLOW YL PK YELLOW WITH PINK STRIPE POWER AND CONTROLS WIRING DIAGRAM DBH 090 120 LINE VOLTAGE 208 230...

Page 43: ...G IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT...

Page 44: ...44...

Page 45: ...45...

Page 46: ...46 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 47: ...47 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 48: ...2020 19001 Kermier Rd Waller TX 77484 www daikincomfort com CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikincom...

Reviews: