APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
HORIZONTAL
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
2784
1.30
2582 0.83
2411
0.79
0.4
2814
1.34
2620
1.19
2342 0.72
2105
0.66
0.6
2665 1.34
2583
1.19
2398
1.06
2103 0.62
1902
0.57
0.8
2689 1.38
2492 1.22
2370
1.07
2142
0.91
1816 0.51
1.0
2438 1.22
2275 1.09
2098
0.92
1883
0.78
1.2
2250 1.10
1996 0.92
NOTES:
Table represents dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
DCC/H072 HIGH STATIC BELT DRIVE HORIZONTAL
(INCLUDES 2 SPEED MOTOR ON HIGH SPEED)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
2746
1.38
2515
1.12
0.8
2721
1.47
2494
1.21
2261
0.97
1.0
2689
1.56
2500
1.32
2255
1.06
1994
0.83
1.2
2752
1.74
2473
1.40
2252
1.15
1996
0.91
1.4
2802
1.88
2487
1.53
2286
1.27
2037
1.02
1.6
2553
1.67
2308
1.40
1997
1.08
1.8
2355
1.51
2014
1.19
2
2055
1.29
NOTES:
Table represents dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
APPENDIX A ECONOMIZER PRESSURE DROP
SCFM
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
in. WG
0.02
0.04
0.05
0.07
0.09
0.12
0.14
0.17
0.21
0.24
0.28
Airflow Pressure Drop of Downflow Economizer for 3 to 6 Ton Rooftop Units (100% Return Air)