16
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC
NOTES:
High static airflow requires installation of high static kit.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.0
---
---
---
---
---
---
---
---
---
---
7120
3.26
6223
2.55
1.2
---
---
---
---
---
---
---
---
6927
3.39
5924
2.61
---
---
1.4
---
---
---
---
---
---
6739
3.52
5602
2.65
---
---
---
---
1.6
---
---
---
---
6587
3.69
5245
2.67
---
---
---
---
---
---
1.8
---
---
6419
3.84
4877
2.70
---
---
---
---
---
---
---
---
2.0
6261
4.01
---
---
---
---
---
---
---
---
---
---
---
---
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.0
---
---
---
---
---
---
---
---
9090
5.79
8297
5.06
7479
3.62
1.2
---
---
---
---
---
---
8774
5.60
7914
4.83
6989
4.07
---
---
1.4
---
---
---
---
8471
5.43
7549
4.63
---
---
---
---
---
---
1.6
---
---
8209
6.14
7194
4.45
---
---
---
---
---
---
---
---
1.8
7967
6.02
6883
5.01
---
---
---
---
---
---
---
---
---
---
2.0
6594
4.87
---
---
---
---
---
---
---
---
---
---
---
---
DCC240 HIGH STATIC BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6
DCC180 HIGH STATIC BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.6
---
---
---
---
---
---
---
---
---
---
---
---
11409
7.12
0.8
---
---
---
---
---
---
---
---
---
---
---
---
10302
6.46
1.0
---
---
---
---
---
---
---
---
---
---
10159
6.79
9195
5.79
1.2
---
---
---
---
---
---
---
---
9990
7.11
8961
6.04
8087
5.13
1.4
---
---
---
---
---
---
9789
7.39
8686
6.25
7763
5.29
6980
4.46
1.6
---
---
---
---
9543
7.63
8357
6.40
7382
5.39
6566
4.53
---
---
1.8
---
---
---
---
7957
6.48
6925
5.41
6077
4.53
---
---
---
---
2.0
---
---
7667
6.68
6370
5.34
---
---
---
---
---
---
---
---
2.2
7280
6.78
---
---
---
---
---
---
---
---
---
---
---
---
DCC300 HIGH STATIC BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0
1
2
3
4
5
6