background image

18

If the venter motor comes on, but the unit does not attempt igni-
tion, check if the ALS (Auxiliary High Limit Control Switch) requires
resetting.

1. With electricity and gas turned on, the system switch in

the “HEAT” or “AUTO” position and the fan switch in the
“AUTO” position, the thermostat will close the circuit
between unit terminals R and W (R-W) when the
temperature falls below the thermostat setting.

2. D1 on IIC energizes relay IDMR.
3. Relay IDMR energizes the venter motor IDM.
4. Operation of the venter motor closes the pressure switch

PS located in the burner compartment. Unless excessive
temperatures or shipping shock have opened high limit
control ALS, power is fed to the integrated ignition control,
which then initiates a 15-second pre-purge time delay.
During this period, the venter motor will clear the
combustion chamber of any residual gas.

5. After the pre-purge period, the ignition control energizes

the Wl-C gas valve and simultaneously initiates a “three
(3)-try” spark ignition sequence.

6. When the burners are ignited, a minimum one (1) micro-

amp DC current will flow through the flame between the
sensor electrode and the grounded burner.

7. When the controller proves that the flame has been

established, it will keep the gas valve energized and
discontinue the ignition spark. High stage manifold
pressure will be approximately 3.5" w.c. for natural gas
and 10.0" w.c. for propane (LP). Low fire natural gas is 2.0”
w.c.; low fire propane 6.0” w.c.

8. If the control is unable to ignite the burners after its initial

attempt, it will initiate another purge and spark sequence.
A third purge and spark sequence will be initiated if the
second attempt is unsuccessful. If the third attempt is
unsuccessful, the controller will close the gas valve and
lock itself out. It may be reset by momentarily interrupting
power. This may be accomplished by briefly lowering the
room thermostat set-point below room temperature, or
by shutting off the main power to the unit. (See TP-105
for more details.)

9. Integrated ignition control will close its normally open

contacts after a delay of approximately 30 seconds. This
action energizes contactor BC and starts the supply fan
motor. Operation of the supply fan circulates air across
the heat exchanger and delivers heated air to the
conditioned space.

10. When the space temperature rises, the thermostat will

open R-W. Opening R-W will cause the gas valve to close,
and the furnace to shut down.

11. The furnace has three high temperature limit controls,

which can shut down the burner. They do not shut down
the venter motor.

Unit Shutdown

1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the unit.
3. Remove the heat exchanger door on the side of the unit

by removing screws.

4. Move the gas control valve switch to the OFF position. Do

not force.

5. Close manual gas shut off valve external to the unit.
6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be  desired, turn ON

the electrical power.

A

UTOMATIC

 R

ESET

 H

IGH

 L

IMIT

 C

ONTROL

 (LS)

Located in the burner compartment on the heat exchanger, its sens-
ing element projects through the blower section bulkhead and
senses the temperature at the rear of the furnace. It will cycle the
furnace off if the temperature exceeds 100°F plus maximum rise.

A

UXILIARY

 H

IGH

 L

IMIT

 C

ONTROL

 (ALS)

Located in the blower compartment on the blower housing, it
senses air temperature within the blower compartment and  pro-
tects the filters from excessive temperature. It will shut down the
furnace if it senses excessive temperatures.

Elevated temperatures at the control are normally caused by
blower failure. The reason for the opening should be determined
and repaired prior to resetting.

M

ANUAL

 R

ESET

 F

LAME

 R

OLLOUT

 C

ONTROL

 (RS)

Located in the burner compartment at the top of the burner as-
sembly, it senses high temperature that could occur if the heat
exchanger tubes were plugged and the flame was rolling out in-
stead of entering the tubes. It has a manual push-button reset that
cannot be actuated until the limit control has cooled.

The reason for elevated temperatures at the control should be
determined and repaired prior to resetting this manual reset con-
trol.

WARNING

T

O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE

OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR

THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING

THE ROLLOUT PROTECTION DEVICE.

R

EFRIGERATION

 S

YSTEM

 C

HECKS

This unit is equipped with a piston type metering device or non-
adjustable TXV.

Ensure the hold-down bolts on the compressor are secure and have
not vibrated loose during shipment.  Check that the vibration grom-
mets have been installed and visually check all piping for damage
and leaks and repair if necessary.  The entire system has been fac-
tory charged and tested, making it unnecessary to field charge.
Factory refrigerant charge is shown on the unit’s nameplate.

To confirm charge levels or, if a leak occurs and charge needs to be
added to the system, it is recommended to evacuate the system
and recharge refrigerant to the unit’s nameplate specifications.
This unit has been rated in the cooling mode at the AHRI rated
conditions of:  indoor (80°F db/67°F wb) and outdoor (95°F db).
While operating at this condition, the superheat should range from
9°F to 11°F for each refrigeration circuit measured at the suction
service port located near the compressor.

Summary of Contents for DCG Series

Page 1: ...MERCIAL PACKAGED GAS UNIT 3 to 6 TON 2013 2016 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com Our continuing commitment to quality products may mean a change in specifications wit...

Page 2: ...FIED IN THIS MANUAL OR ATTEMPTING TO INSTALL ADJUST SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEA...

Page 3: ...ould be greater than or equal to the design heating and cooling loads of the area to be conditioned The loads should be calculated by an approved method or in accordance with ASHRAE Guide or Manual J...

Page 4: ...ial and industrial processes may also be sources of chlorine fluorine compounds To avoid possible illness or death of the building occupants do NOT locate outside air intake device economizer manual f...

Page 5: ...l perimeter curbs include duct connection frames to be assembled with the curb Cantilevered type curbs are not available from the factory Curb insulation cant strips flashing and general roofing mater...

Page 6: ...S 42 TO PREVENT DAMAGE TO THE UNIT HOWEVER 48 IS RECOMMENDED CAUTION Provisions for forks have been included in the unit base frame No other fork locations are approved WARNING TO PREVENT POSSIBLE EQU...

Page 7: ...WIRING OF THESE UNITS ARE FACTORY INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT CONTACT YOUR LOCAL REPRESENTATIVE IF ASSISTANCE IS REQUIRED WARNING TO PREVENT DAMAGE TO THE WIRING PROTE...

Page 8: ...ING Areas Without Convenience Outlet It is recommended that an independent 115V power source be brought to the vicinity of the roof top unit for portable lights and tools used by the service mechanic...

Page 9: ...m Value Shown in Table Above The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition In addition gas input to...

Page 10: ...line by loosening the ground joint union until pure gas is expelled Tighten union and wait for five minutes until all gas has been dissipated in the air Be certain there is no open flame in the vicini...

Page 11: ...If the gas pressure at the unit is greater than 10 5 w c the contractor must furnish and install an external type positive shut off service pressure regulator The unit will not function satisfactorily...

Page 12: ...MACHINERY HAZARD TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DISCONNECT POWER TO THE UNIT AND PADLOCK IN THE OFF POSITION BEFORE SERVICNG FANS WARNING This unit is equipped with an electronic igniti...

Page 13: ...pply voltage will be main tained within the utilization range under all system conditions check and calculate if an unbalanced condition exists between phases Calculate percent voltage unbalance as fo...

Page 14: ...tor and bearing failure will occur Check you belt drive for adequate run in belt tension by measuring the force required to deflect the belt at the midpoint of the span length Belt tension force can b...

Page 15: ...when the furnace is in operation An inspection port in the access panel is provided to monitor the flame The first step in checking out the gas fired furnace is to test the gas supply piping to the u...

Page 16: ...R W1 and W2 on TB1 Place jumper wire between R W1 and W2 to engage high stage heat note on 045 kbtu hr units W2 is not used only jumper R to W1 2 See Figure in input rating section for gas valve adjus...

Page 17: ...EVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULAT...

Page 18: ...ing 2 Turn off the electrical power supply to the unit 3 Remove the heat exchanger door on the side of the unit by removing screws 4 Move the gas control valve switch to the OFF position Do not force...

Page 19: ...1 or M2 Black High Speed Blue Medium Speed Red Low Speed EEM Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the motor terminal block White is for fan only and g...

Page 20: ...ly matted on the entering air face of the coil and can be removed by brushing 3 Lubricate motor bearings 4 Align or replace belts as needed 5 Replace filters as needed see below 6 Check for blockage o...

Page 21: ...ng the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit which is held by two screws If you are uncertain abo...

Page 22: ...n the gas valve is deenergized the circulator blower heat off cycle begins and the induced draft blower remains on The diagnostic fault code is two flashes Pressure Switch Stuck Closed 3 FLASH CODE A...

Page 23: ...EXTERNAL STATIC PRESSURE ESP in w c STANDARD CFM AMPS WATTS RPM 0 10 1293 1 72 364 715 0 20 1235 1 67 354 759 0 30 1173 1 62 342 803 0 40 1124 1 58 330 841 0 50 1056 1 54 316 880 0 60 978 1 47 298 913...

Page 24: ...SPEED TAP EXTERNAL STATIC PRESSURE ESP in w c STANDARD CFM AMPS WATTS RPM 0 10 1612 2 60 554 789 0 20 1548 2 49 532 832 0 30 1484 2 38 510 875 0 40 1400 2 27 486 904 0 50 1316 2 16 462 933 0 10 1846...

Page 25: ...626 1008 0 70 1688 5 05 642 1039 0 10 2106 5 14 650 924 0 20 2050 5 26 670 951 0 30 1993 5 32 678 969 0 40 1960 5 47 696 1001 0 50 1920 5 54 706 1021 0 60 1880 5 61 726 1041 0 70 1810 5 73 736 1072 0...

Page 26: ...4 58 582 940 0 70 1782 4 72 602 968 0 10 2224 4 73 592 832 0 20 2165 4 79 612 860 0 30 2123 4 91 630 891 0 40 2079 5 01 642 913 0 50 2029 5 14 666 946 0 60 1978 5 26 676 969 0 70 1926 5 38 698 1001 0...

Page 27: ...M BHP 0 2 2210 0 91 2041 0 76 1869 0 63 1739 0 52 1565 0 40 0 4 2197 0 98 2021 0 82 1841 0 67 1660 0 54 1521 0 44 1339 0 32 0 6 2002 0 88 1822 0 72 1635 0 58 1445 0 44 1288 0 35 0 8 1799 0 77 1610 0 6...

Page 28: ...OWN SHOT CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2262 1 16 2051 0 95 1851 0 76 1657 0 60 0 8 2277 1 27 2070 1 05 1852 0 84 1646 0 66 1 0 2304 1 39 2089 1 15 1872 0 93 1647 0 72 1 2 2104 1...

Page 29: ...CFM BHP CFM BHP CFM BHP 0 2 2460 0 96 2251 0 80 2073 0 65 1862 0 51 0 4 2408 1 00 2206 0 84 1982 0 68 1808 0 55 1572 0 41 0 6 2402 1 08 2173 0 89 1943 0 72 1701 0 55 1511 0 43 0 8 2153 0 95 1917 0 77...

Page 30: ...M BHP CFM BHP CFM BHP CFM BHP CFM BHP 0 6 2219 0 95 1970 0 75 0 8 2215 1 04 1956 0 82 1697 0 62 1 0 2240 1 15 1957 0 90 1681 0 67 1 2 2260 1 26 1983 1 00 1683 0 74 1 4 2288 1 38 2009 1 10 1711 0 84 1...

Page 31: ...0 7 6 BD STD STATIC 1 0 3 8 460 60 3 414 506 1 7 76 52 0 1 1 4 0 80 BD STD STATIC 1 0 1 9 575 60 3 518 633 1 5 71 38 9 1 1 4 0 60 BD STD STATIC 1 5 2 3 208 230 60 3 187 253 1 19 123 1 1 3 1 92 BD STD...

Page 32: ...6 1 4 4 7 8 DRAIN THRU CURB LOCATION EMBOSS FOR THRU THE BASE UTILITIES BOTTOM VIEW OF UNIT 8 3 16 5 7 8 19 7 16 27 3 8 47 1 2 4 1 2 7 1 2 SUPPLY RETURN 73 1 4 47 1 2 74 1 16 48 3 16 38 13 16 6 Ton 4...

Page 33: ...YL 208 240 1 60 SEE NOTE 5 RD YL RD IIC C RD YL L2 C T2 L1 T1 BK BK PU RD OR YL SEE NOTE 8 GREEN JUMPER ALS PS RS PLF YL YL NOTE 4 GAS VALVE MV PU W R GAS VALVE PU ALT HONEYWELL BL BR PU PU PU BK R G...

Page 34: ...898 A HPS LPS HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL HIGH VOLTAGE LOW VOLTAGE FIELD WIRING LINE VOLTAGE LOW VOLTAGE BL RD Y1 YL W BL G R W NO ECONOMIZER G YL RD Y1 PK WH W R RD...

Page 35: ...EE NOTE 5 RD YL RD IIC C RD YL L2 C T2 L1 T1 BK BK PU RD OR YL SEE NOTE 8 GREEN JUMPER ALS GR PS RS PLF YL YL NOTE 4 GAS VALVE MV BL W R GAS VALVE PU ALT HONEYWELL BR PU PU PU BK BR R G Y1W1 OR RD C M...

Page 36: ...GEND COMP ALS TB1 TR TRANSFORMER 208 240 1 60 0140L02900 A HPS LPS HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL HIGH VOLTAGE LOW VOLTAGE FIELD WIRING LINE VOLTAGE LOW VOLTAGE BL RD Y1...

Page 37: ...NOTE 5 RD YL R D IIC C RD RD L2 C T2 L1 T1 BK BK PU YL OR YL SEE NOTE 8 GREEN JUMPER ALS GR PS RS PLF YL YL NOTE 4 GAS VALVE MV BL W R GAS VALVE PU ALT HONEYWELL BR PU PU PU BK BR R G Y1 W1 OR RD C M...

Page 38: ...0 3 60 0140L02899 A HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL HIGH VOLTAGE LOW VOLTAGE FIELD WIRING LINE VOLTAGE LOW VOLTAGE BL RD Y1 YL W BL G R W NO ECONOMIZER G RD Y1 PK WH W R...

Page 39: ...K PU YL OR YL RD RD RD BK SEE NOTE 8 GREEN JUMPER BL BK YL YL PU BR BL RD PU WH GR BL ALS GR PS RS PLF YL YL NOTE 4 GAS VALVE MV 2 1 4 5 YL BL W R GAS VALVE PU ALT HONEYWELL 3 6 YL BR PU PU PU BK BR O...

Page 40: ...IGN IIC EM L2 L3 COMPRESSOR COMPONENT LEGEND COMP ALS TR TRANSFORMER C CM T3 T3 T2 FC C T1 T1 C T2 208 240 3 60 0140L02902 A HPS LPS HPS HIGH PRESSURE SWITCH HIGH VOLTAGE FACTORY WIRING OPTIONAL HIGH...

Page 41: ...NOTE 8 NOTE 8 POWER SUPPLY 240 1 60 BL L2 C T2 L1 T1 NOTE 2 COMP CM VMR C 24V TR LS NOTE 6 SEE ALS PS RS GAS VALVE MV 2 1 4 5 W R GAS VALVE ALT HONEYWELL 3 6 1 2 3 MV GV GV TB1 LPS HPS 1 5 EM Y2Y1 GND...

Page 42: ...VICEMAN STATUS LIGHT 3 BLINKS 6 BLINKS 2 BLINKS 4 BLINKS 5 BLINKS OFF ON 1 BLINK OPEN AUX LIMIT FALSE FLAME SENSED OUTPUT DELAY OPEN LIMIT SWITCH COMPRESSOR WITHOUT INDUCER ON PRESSURE SWITCH SWITCH O...

Page 43: ...C T2 T3 L3 L1 T1 BK BK PU YL COMP BK PU CM BR VMR OR YL RD RD YL YL PU RD BL RD ALS GR PS RS PLF YL YL NOTE 4 BR WH PU PU BK YL GR TB1 WH YL NOTE 3 7 1 5 3 2 1 RD RD LS 208 TR BL 24V C BL PK 240 BL N...

Page 44: ...3 60 SUPPLY VOLTAGE CM CONDENSER MOTOR NOTE 6 FS IIC L2 VM 1 VMR L3 LS LIMIT SWITCH VENT MOTOR RELAY VENT MOTOR PRESSURE SWITCH TERMINAL BLOCK 24V SIGNAL ROLLOUT SWITCH VMR VM PS PLF TB1 RS NOTES FAN...

Page 45: ...1 240 2 3 C BK OR RD OR BL GR SEE NOTE 3 FS IGN BK VM OR RD FC RD BR RD T2 T3 T1 C BC BK 208 L3 L2 L1 WH YL HPS LPS PK TB1 YL PK BL PK GR RD TO THERMOSTAT 3 1 2 F C OR OR SEE NOTE 4 BK BK BK GND T3 RD...

Page 46: ...LUE PU PURPLE PK PINK WH WHITE BK BLACK RD RED BR BROWN OR ORANGE YL YELLOW VM 5 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER INSTALLER SERVICEMAN FA...

Page 47: ...Y YL BK 208 240 3 60 YL IIC T1 T2 BK PU YL BK RD C L1 L2 BL BL RD RD BK PU COMP CM BR BK RD RD LS WH GR BL PU RD RD YL RD YL GR YL PU YL PU PS NOTE 2 PLF YL ALS OR RD BK OR EM WH VMR BL 24V TR BL BL 1...

Page 48: ...ALS PS 10 3 6 8 12 11 9 IIC 7 TR 1 4 208 240 3 60 0140L02894 A LPS HPS LPS LOW PRESSURE SWITCH HPS HIGH PRESSURE SWITCH BC BC 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT USE NEC CLASS 2 WIRE 2 ACCESSORY E...

Page 49: ...60 SEE NOTE 4 POWER SUPPLY GR YL PK BL PK OR WH BK OR L3 L2 L1 LPS HPS OR RD BK BC C T3 T1 T2 PK RD BR BR RD FC RD OR VM BK IGN FS NOTE 3 SEE YL OR BK 460 575 TR 240 C 460 BL BL TR 24V BL VMR 3 1 2 W...

Page 50: ...n the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PE...

Page 51: ...R RD FC RD BR SMOKE FIRE DETECTOR REPLACES JUMPER WIRE HPS BL PK GND T3 RD OR L3 YL BK GR YL IIC T1 T2 BK PU YL BK RD C L1 L2 BL BL RD OR BK BK PU COMP CM BR BK RD RD LS WH GR BL PU RD RD RD WH BR YL...

Page 52: ...TAGE FIELD WIRING HIGH VOLTAGE OPTIONAL HIGH VOLTAGE ALS COMP COMPONENT LEGEND COMPRESSOR EM IIC IGN GND FS GV C F FUSE FC EVAPORATOR MOTOR FLAME SENSOR EQUIPMENT GROUND IGNITOR GAS VALVE CONTACTOR FA...

Page 53: ...M 2 STAGE COMP BL CC BC1 BC2 CS PU PK AUX B AUX A 8 18 7 Y Y R B SENSOR 2 Y Y R B SEN2 PK OPTIONAL SMOKE DETECTOR Y Y R B 24V AC DC SENSOR 1 9 10 Y Y R B 16 6 17 SEN1 RD BR BL 5 BL C R 1 S 2 S RD BK R...

Page 54: ...FLAME SENSER GAS VALVE GAS PRESSURE GAS FLOW REPLACE CONTROL CHECK FUSE ON CONTROL CHEC K INPUT POWER DELAY COMPRESSOR OUTPUT FALSE FLAME SENSED OPEN LIMIT SWITCH WITHOUT INDUCE R ON PRESSU RE SW ITCH...

Page 55: ...OMPRESSOR OUTPUT FALSE FLAME SENSED OPEN LIMIT SWITCH WITHOUT INDUCER ON PRESSUR E SW ITCH CLOSED PRESSURE SWITCH OPEN OPEN AUX LIMIT SWITCH OPEN ROLLOUT SWITCH IGNITION FAILURE INTERNAL CONTROL NO PO...

Page 56: ...56 WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLS ARE LOCATED IN SUPPLEMENT IOD S1004 For complete information and installation instructions for models with DDC controls see manual DK DDC TGD 01A...

Page 57: ...tension and alignment per installation instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp...

Page 58: ...Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Cir...

Page 59: ...59 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 60: ...60 2013 2016 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com Our continuing commitment to quality products may mean a change in specifications without notice...

Reviews: