4
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the
carrier. The carrier is responsible for making prompt
inspection of damage and for a thorough investigation
of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, re-
move all packaging materials. Recycle or dispose of the packaging
material according to local codes.
P
RE
-I
NSTALLATION
C
HECKS
Carefully read all instructions for the installation prior to installing
unit. Ensure each step or procedure is understood and any special
considerations are taken into account before starting installation.
Assemble all tools, hardware and supplies needed to complete the
installation. Some items may need to be purchased locally.
UNIT LOCATION
T
O
PREVENT
POSSIBLE
EQUIPMENT
DAMAGE
,
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
,
THE
FOLLOWING
BULLET
POINTS
MUST
BE
OBSERVED
WHEN
INSTALLING
THE
UNIT
.
WARNING
IMPORTANT NOTE: Remove wood shipping rails prior to installa-
tion of the unit. See important note under Roof Curb Installation
Only.
A
LL
I
NSTALLATIONS
:
I
MPORTANT
N
OTE
: Unit should be energized 24 hours prior to
compressor start up to ensure crankcase heater has suffi-
ciently warmed the compressors. Compressor damage may
occur if this step is not followed.
NOTE:
This appliance is a dedicated downflow design.
Proper installation of the unit ensures trouble-free operation. Im-
proper installation can result in problems ranging from noisy
operation to property or equipment damages, dangerous condi-
tions that could result in injury or personal property damage and
could void the warranty. Give this booklet to the user and explain
it’s provisions. The user should retain these instructions for future
reference.
•
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted
level.
•
The flue outlet must be at least 12 inches from any opening
through which flue gases could enter a building, and at
least three feet above any forced air inlet located within
ten feet. The economizer/manual fresh air intake/
motorized fresh air intake and combustion air inlet
mounted on the unit are not affected by this restriction.
•
To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e.
combustion air for the unit) will be frequently
contaminated by compounds containing chlorine or
fluorine. Common sources of such compounds include
swimming pool chemicals and chlorine bleaches, paint
stripper, adhesives, paints, varnishes, sealers, waxes (which
are not yet dried) and solvents used during construction
and remodeling. Various commercial and industrial
processes may also be sources of chlorine/fluorine
compounds.
•
To avoid possible illness or death of the building occupants,
do NOT locate outside air intake device (economizer,
manual fresh air intake, motorized fresh air intake) too
close to an exhaust outlet, gas vent termination, or
plumbing vent outlet. For specific distances required,
consult local codes.
•
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see unit
clearances). These clearances must be permanently
maintained.
•
The combustion air inlet and flue outlet on the unit must
never be obstructed. If used, do not allow the economizer/
manual fresh air damper/ motorized fresh air damper to
become blocked by snow or debris. In some climates or
locations, it may be necessary to elevate the unit to avoid
these problems.
•
When the unit is heating, the temperature of the return
air entering the unit must be between 50° F and 100° F.
G
ROUND
L
EVEL
I
NSTALLATIONS
O
NLY
:
•
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended.
Prepare a base that is 3” larger than the package unit
footprint and a minimum of 3” thick.
•
The base should also be located where no runoff of water
from higher ground can collect in the unit.
R
OOF
TOP
I
NSTALLATIONS
O
NLY
:
•
To avoid possible property damage or personal injury, the
roof must have sufficient structural strength to carry the
weight of the unit(s) and snow or water loads as required
by local codes. Consult a structural engineer to determine
the weight capabilities of the roof.
•
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
•
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
•
As indicated on the unit data plate, a minimum clearance
of 36” to any combustible material is required on the
furnace access side of the unit. All combustible materials
must be kept out of this area.
•
This 36” clearance must also be maintained to insure
proper combustion air and flue gas flow. The combustion
air intake and furnace flue discharge must not be blocked
for any reason, including blockage by snow.
•
Adequate clearances from the furnace flue discharge to
any adjacent public walkways, adjacent buildings, building
openings or openable windows must be maintained in
accordance with the latest edition of the National Fuel Gas
Code (ANSI Z223.1)