PRODUCT DESIGN
34
3
4
Add 5%
OF F
OFF
Minus 5%
ON
OFF
Add 10%
OF F
O N
Minus10%
ON
O N
Trim Amount
SWITCH
S3
DISABLE
OFF
ENABLE
ON
SWITCH 2
Trim Enable
S5
AIR FLOW DATA
NOTE:
Airflow data shown applies to non-communicating mode operation only. For a fully communicating system, please
see the outdoor unit’s installation instructions for cooling and pump heating airflow data.
See
ComfortNet™ System - Airflow Consideration
section for details.
TAP
S3-1
S3-2
S3-3
S3-4
S4-1
S4-2
S4-3
S4-4
A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
B
ON
OFF
On
OFF
On
OFF
On
OFF
C
OFF
ON
OFF
ON
OFF
ON
OFF
ON
D
ON
ON
ON
ON
ON
ON
ON
ON
Profiles
A
B
C
D
Speed Selection Dip Switches
Heat
Selection
Switches
Pre-Run
Short-Run
OFF Delay
Cool
Selection
Switches
Adjust
Selection
Switches
Profil e
Selection
Switches
------------
------------
------------
------------------
To Set Ai rfl ow: (1) Sel ect mo del and d esir ed Hi gh Stag e Coo li ng Airfl ow. D etermi ne the
corre spon di ng tap (A, B, C, o r D). Se t di p swi tch es S3-1* a nd S3 -2* to th e app rop riate ON/OFF
po sition s. (2 ) Se lect mode l an d desi red H ig h Sta ge He atin g Airflo w. De termin e th e
corre spon di ng tap (A, B, C, o r D). Se t di p swi tch es S4-3* a nd S4 -4* to th e app rop riate ON/OFF
po sition s. (3 ) Se lecti ng Air fl ow Adju stme nt Fa cto r: For 0% trim set S5-2* to OFF (trim disa bl ed).
If trim is desi red se t S5-2 * to ON (trim en abl ed ) a nd set S3-3 * and S3 -4* to ap prop ria te ON/OFF
po sition s. Tap A is +5%, Ta p B i s -5%, Ta p C is +10%, Tap D is -1 0%.
To Set C omfo rt Mo de: Sele ct D esire d Comfort Mode p rofil e (see p rofil es ab ove). Set d ip
switch es S4-1* a nd S4-2 * to th e app rop riate ON/OFF posi tion s.
De humid ifica ti on : To en abl e, se t swi tch S5-1* to ON. C oo lin g ai rfl ow wi ll b e redu ced to 85 % of
no mi na l valu e du ring cool ca ll . To di sabl e, set sw itch S5-1* to OFF.
Co ntinu ous Fan Sp eed : Set di p switche s S5 -3* a nd S5-4 * to se le ct on e of 4 contin uo us fa n
spe eds (25 %, 5 0%, 75 %, o r 1 00% ). "Se e insta lla tion ma nua l fo r detai ls."
*the "S" n umber refe rs to on e of fo ur la bel ed d ip swi tch se ction s,
ea ch contai ni ng 4 i ndi vid ual d ip sw itches.
The foll owi ng n umbe r re fe rs to the i nd ivid ua l lab eled di p swi tch w ithi n th at se cti on .
60 sec/100%
60 sec/100%
60 sec/100%
30 sec/50%
30 sec/50%
30 sec/50%
7.5 min/82%
7.5 min/82%
0140F01786
Model
TAP
Low
Stage
Cool
High
Stage
Cool
Low
Stage
Heat
High
Stage
Heat
DD80VC0603B***
A
B
C
D
390
520
650
780
600
800
1000
1200
735
805
875
945
1050
1150
1250
1350
DD80VC0805C***
A
B
C
D
520
715
910
1170
800
1100
1400
1800
945
1015
1085
1155
1350
1450
1550
1650
DD80VC1005C***
A
B
C
D
553
748
943
1203
850
1150
1450
1850
1085
1115
1225
1260
1550
1650
1750
1800
DM80VC0604B***
A
B
C
D
390
520
715
910
600
800
1100
1400
875
945
1015
1085
1250
1350
1450
1550
DM80VC0805C***
A
B
C
D
520
715
910
1170
800
1100
1400
1800
1050
1120
1190
1260
1500
1600
1700
1800
DM80VC1005C***
A
B
C
D
520
715
910
1170
800
1100
1400
1800
1210
1225
1245
1260
1725
1750
1775
1800
•
Profile D
ramps up to 50% of the demand for 1/2
minute, then ramps to 85% of the full cooling demand
airflow and operates there for approximately 7 1/2 min-
utes. The motor then steps up to the full demand air-
flow. Profile D has a 1/2 minute at 50% airflow OFF
delay.
OFF
OFF