IM
1133-C
DIII-NET COMMUNICATION GATEWAY
12
www.DaikinApplied.com
Integration
Once the DIII-NET Communication Gateway has been properly installed on the unit and connected to a DIII network, it is then
possible to integrate the unit controller with a Daikin Intelligent Touch Controller or iTouch Manager over a DIII network. The
integration process is described in the following section.
Configuring the DIII-NET Communication Gateway
The MicroTech III Applied Air Handling Unit Controller and optional DIII-NET Communication Gateways are designed,
programmed, and configured at the factory. However, the DIII-NET Communication Gateway needs to have a unique indoor
unit address compatible with the existing DIII network. This address and any other configurations can be set through the keypad
on the MicroTech III Unit Controller. The unit is ready to operate with the default parameter values in the unit controller even
before you change the default parameters for your particular network. Appendix B lists the menu items for the “D3 Set-Up
Menu” and “D3 Status Menu.”
Note:
Refer to Operation Manual OM 920 for details regarding the MicroTech III Applied Air Handling Unit Controller
keypad/display. Manual is available at
www.DaikinApplied.com