background image

- 15 - 

Check  that  vibration  isolator  mounts  are 
functioning well. 

Inspect  for  any  obstructions  or  blockages 
at air intakes and discharges. 

Check  fan  bearings  are  secured  and  no 
undue noise by observe/listen using metal 
bar as a conductor. 

If  unit  equipped  with  belt  guard,  check 
that it is fitted correctly and secure. 

If  there  is  any  undue  noise  or  knocking 
from  bearing,  replace  both  bearings.  Fan 

bearing are grease for life, but larger units

 

with standard bearing require semi-annual 
or  annual  lubrication  at  bearing  greasing 

nipple.  Recommended  lubricants  are 
Standard Din 51823, K3N or ISO XM2.

 

 
7.2 Drive Belt 

 

Belts that are split or have frayed edges or 

any  other  sign  of  damage  (rubber  shred 
on floor) must be replaced in full set.  

 

IMPORTANT 

DURING 

MAINTENANCE 

AND 

SERVICING, 

UNIT 

MUST 

BE 

COMPLETELY 

ISOLATED 

AND 

PRECAUTIONS 

TAKEN 

TO 

PREVENT 

ACCIDENT 

FROM 

HAPPENING. 

 

Check the belt tension and alignment, re-
tension and re-align if necessary. Refer to 
Section  5.7  for  belt  tensioning  procedure. 

New belt drive must be re-tensioned after 
the first 48 hours of operation.

 

For replacement of belts, remove the belt 
guard before starting work. To change the 

belts, first loosen the adjusting screw and 
move the motor towards the fan to enable 
old  belts  to  be  taken  off  and  put  on  of 

new  belts.  (Matched  belts  must  be  used) 
Tension  the  belts  by  following  instruction 

at Section 5.7. 

 
7.3 Coil Section 

Periodic cleaning of coils is required. Dirty 
coils  have  tendency  to  increase  airside 

pressure drops and reduce cooling/heating 
efficiency. Dry cleaning is done by using a 
powerful  vacuum  cleaner  on  the  dust-

accumulated side. If coil is very dirty, coils 
need  to  be  removed  for  wet  cleaning  by 

trained personnel. Ensure coil fins are not 
damage 

when 

performing 

dry/wet 

cleaning. In the event that fin edges have 
been bent, treat with aid of a coil comb. 
Check  that  frost  protection  is  working 

before  starting  of  each  winter  season. 
Ensure  the  frost  sensor  is  correctly 
installed  and  working  within  desired 
temperature range. 
For direct expansion coils,  do not use hot 

water or steam to clean these coils. During 
normal  operation,  the  fin  block  must  not 

be  ice  up.  If  this  occurs,  check  the 
refrigeration system. 

Check  that  drain  pan  and  drain  trap  are 
free 

from 

blockage 

and 

water 

accumulation at pan. 

 
7.4 Filter Section 

 

During system start up, filters are likely to 

become rapidly blocked.  

 

Disposable  filters  and  bag  filters  must  be 
replaced  each  time  when  pressure  drop 

reaches  the  indicated  dirty  condition  by 
D.M. Manometer. Washable filters must be 
cleaned periodically. 

 

7.5 Dampers 

 

Check  for  dirt  accumulation,  damage  and 
sign of corrosion. Clean with cloth or high 

pressure  air.  Check  damper  blade  turning 
manually  or  central  control  for  smooth 
operation. 

 

Table 4 - Recommended Maintenance intervals (based on 12 hours operating time per day) 

Component 

Description 

Action 

Maintenance interval 

Weekly  Monthly  3 Monthly  6 Monthly  Yearly 

Fan / Motor 

Fan in general 

Check / Clean 

● 

 

 

 

 

 

Fan bearing 

Check / Replace / Greasing 

 

 

 

● 

 

 

Motor in general 

Check / Clean 

 

● 

 

 

 

 

Motor bearing 

Check 

 

 

 

● 

 

 

Motor temperature  

Check / Repair / Replace fan 

 

 

 

● 

 

 

Belt drive tension 

Check / Re-tension 

 

● 

 

 

 

 

V-Belt condition 

Check / Replace 

 

● 

 

 

 

 

Corrosion 

Check / Treat / Repair 

 

● 

 

 

 

 

Bolt & nut secure 

Check / Tighten 

 

 

 

● 

 

Summary of Contents for DM AHU

Page 1: ...LATION OPERATION MAINTENANCE VER O AHU01 DEC20 15 The design and construction are subject to change without any notice for future improvement MODELS DM AHU DS AHU AHUR VRV AHU Double Skin Modular Air...

Page 2: ...rtificate which is determined by International National or Local Codes and Regulation Place of service should be equipped with the necessary protective equipment which provide safe maintenance 1 4 Uni...

Page 3: ...truck 4 Storage For external storage prior to installation the units must be protected from dust rain constant sun exposure and rodents Although covered in shrink wrapped plastic sheeting this is not...

Page 4: ...carefully assembled to desired unit arrangement The air handling units are design to use section joint brackets to combine two sections Section joints for cabinet and base frame are shown in Figure 5...

Page 5: ...on joint WARNING CABINET SECTION JOINTS ARE NOT INTENDED FOR LIFTING PURPOSE AND PULLING CABINET FROM A DISTANCE TO JOIN SECTION TOGETHER When the cabinets are penta post to penta post arrangement or...

Page 6: ...hipped out from factory See Figure 15 Figure 14 Restrained Spring Isolator Figure 15 Removing of U Shaped Plate 5 5 Arrangement VRV AHU Control box and expansion valve kit are installed on the air han...

Page 7: ...joints or flexible fittings are to be provided in all piping connections particularly those adjacent to heating source to absorb expansion and contraction strains Failure to comply will result in dama...

Page 8: ...valve and not to a common header When two or more coils are connected to a common suction line never place the bulb on the common line Thermostatic expansion valve is to be equipped with external equa...

Page 9: ...r control refer to the VFD manual for wire size and requirements Figure 22 3 phases motor connection diagram 5 7 2 Motor Cabling Motor wiring must go downward from motor terminal box to prevent conden...

Page 10: ...he diameter of smaller pulley Table 2 Adjusted Pitch Diameter Model VPT100Z1 VPT120A1 A2 VPT139A1 A2 VPT156A1 A2 VPT177A1 A2 VPT178B2 Max Pitch mm 96 114 4 133 4 150 4 171 4 171 Min Pitch mm 82 9 96 1...

Page 11: ...ee Table 2 Figure 27 When the required diameter is obtained adjustable flange is locked by tighten the four clamp screws To get the same diameter in the two grooves of pulleys screw the two mobile fla...

Page 12: ...out Notes 1 Elbows should not be closer than 2 1 2 times the Duct Equivalent Diameter Refer to Formula 1 2 Dampers should be placed at least fan diameters downstream of the fan discharge Formula 1 Duc...

Page 13: ...ther For DX coils it is advisable that the refrigerant is to be pumped into the condenser If this is not possible refrigerant shall be purged out WARNING DO NOT HEAT ANY PART ON DX COIL IF REFRIGERANT...

Page 14: ...20mm 6 1 5 Coils Check the pipe work to coil is correctly connected and the fins are free from foreign matter or damage Check that the condensate drain is trap Ensure good sealing of silicon around th...

Page 15: ...or cap screw are in secure position CAUTION HIGH AIR TEMPERATURE IN FAN SECTION CAN CAUSE MOTOR OVERHEAT AND DAMAGE ON DRAW THROUGH AIR HANDLERS ADJUST THE DISCHARGE AIR TEMPERATURE OF THE HEATING SE...

Page 16: ...ling heating efficiency Dry cleaning is done by using a powerful vacuum cleaner on the dust accumulated side If coil is very dirty coils need to be removed for wet cleaning by trained personnel Ensure...

Page 17: ...IR VELOCITY SHOULD NOT BE LOWER THAN 2 0 m s 7 7 Heat Wheel Heat Pipe The unit should be maintained in line with the manufacturer recommendation Please refer installation and maintenance manual for de...

Page 18: ...not evenly supported on foundation j Fan assembly s tolerance is out of range a Consult manufacturer b Remove transport bracket c Check pulley alignment d Re tension belts e Replace vibration isolato...

Page 19: ...he heat wheel baffle top 8 Assembled back the remaining panels 9 2 AHU Water Quality Water quality requirements Water softening treatment must be given in advance to prevent scaling in the heat exchan...

Page 20: ...Yes No 5 Correct incoming voltage that supplied to motor L1 L2 __________ L2 L3 __________ L3 L1 __________ 6 Rotate fan wheel whether it can rotate freely and without abnormal noise Answer Yes No 7 A...

Page 21: ...Are the AHU sections joined with section joint properly Answer Yes No 4 Are the joining between AHU sections sealed properly Answer Yes No Start Up Checking 1 Is fan rotated in correct direction Answe...

Reviews: