SYSTEM OPERATION
11
display will show the next available item in the main menu.
While in the main menu, press the “option” switch to scroll
through available options corresponding to the main menu
item displayed. In the option menu, the default option will
be displayed first. If the default option has been changed
to another option, the current option selection will be
displayed first.
The option menu will display both adjustable & non-
adjustable options. When an adjustable option is
displayed, the display will flash continuously until a switch
is pressed. If a non-adjustable option is displayed (such
as Code Release Number) the display will not flash.
While navigating the option menus, press the menu switch
to select the displayed option. The displayed selection will
stop flashing indicating the selection was made. Press the
menu button again to finalize the selection and return to
the corresponding main menu.
In the option menu, after the last option has been
displayed, the display will revert to the corresponding
main menu & display the default (or selected) option.
If switches are inactive for 30 seconds the display will
revert to the status menu.
Control Board Main Menu
Description
Main Menu
LED
Display
Option Menu
LED Display
Default
Idle - system awaiting
input
i dl
Display Active Alarm
Er r
Display Last 6 Faults
L6F
Code Release Number
Cr
None
Shared Data Revision
Sr
None
Reset to Factory
Default
r Fd
Yes / No
Outdoor Setting Menu
OdS
AC1 / AC2 / HP1 /
HP2 / OFF
OFF
Blower Speed for
Continuous Fan Mode
FSd
F01 - F09
F01
Blower Speed for 1st
Stage Compressor
Mode
AC1
F01 - F09
Model
specific
Blower Speed for 2nd
Stage Compressor
Mode
AC2
F01 - F09
Model
specific
Cooling Fan Off Delay
CFd
0 - 120 seconds
65
seconds
Cooling Fan On Delay
Cnd
0 - 35 seconds
7
seconds
Blower Speed for Gas
Heat Mode
gAF
Allowable speeds Fxx
Model
specific
Gas Heat Off Delay
gFd
30 - 120 seconds
90
seconds
Gas Heat On Delay -
locked
gnd
None
30
seconds
Blower Speed for 1st
Stage HP Heat Mode
HP1
F01 - F09
Model
specific
Blower Speed for 2nd
Stage HP Heat Mode
HP2
F01 - F09
Model
specific
HP Heat Off Delay
HFd
30 - 120 seconds
60
seconds
HP Heat On Delay
Hnd
5 - 30 seconds
5
seconds
See Troubleshooting
chart for alarm code
definition
Control Board Status Menu
LED
Display
Description of System Status
888
All segments illuminated =
control powering up
I DL
Idle
FAn
Constant Fan
1AC
Low Stage Cooling
2AC
High Stage Cooling
1AC
Compressor Heat, Low Stage
2AC
Compressor Heat, High Stage
gH
Gas Heat
1HP
Low Stage HP
2HP
High Stage HP
dFt
Defrost
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode, see
the following steps:
1. Press menu button until LED displays “FSd”. Press
option button and LED will display the currently selected
speed number as Fxx (xx: Blower speed number from
1 to 9).
2. The control shall cycle through available fan speeds
every time the option button is pressed. All 9 speeds
are available for circulation.
3. When the menu button is pressed, the current displayed
speed shall stop flashing. Press the menu button again
to select the option and the control shall immediately
apply that blower setting and return to the corresponding
main menu.
THERMOSTAT CALL AVAILABLE SPEEDS
(FSd menu)
G
F01
F02
F03
F04
F05
F06
F07
F08
F09
Circulation Speed Table
Cooling Mode Speed Selection
To change the main blower speed in COOLING mode,
follow the following steps: