CIRCULATION AIRFLOW DATA

Model

DIP SWITCHES 

S2-3 , S2-4

External Static Pressure, (Inches Water Column)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

DM96SE 

0403A

OFF OFF

715

666

609

558

500

438

386

333

276

220

ON OFF

1110

1081

1042

1003

965

933

893

856

820

803

OFF ON

1191

1168

1135

1112

1081

1055

1024

998

978

N/A

ON ON

1344

1312

1278

1247

1215

1178

1143

1114

1081

1049

DM96SE 

0603B

OFF OFF

785

717

648

587

520

457

400

327

269

206

ON OFF

1240

1194

1153

1104

1069

1019

971

929

893

N/A

OFF ON

1155

1105

1056

1006

958

908

857

808

772

723

ON ON

1384

1338

1300

1257

1215

1169

1125

1080

1040

994

DM96SE 

0803B

OFF OFF

747

676

602

529

453

386

329

281

186

N/A

ON OFF

1206

1157

1111

1059

1009

966

913

863

834

784

OFF ON

1149

1095

1051

1003

951

900

845

812

762

707

ON ON

1414

1380

1333

1305

1260

1223

1180

1137

1091

1047

DM96SE 

0804C

OFF OFF

1010

935

861

785

721

631

553

483

423

350

ON OFF

1621

1570

1521

1467

1414

1378

1327

1274

1221

1167

OFF ON

1826

1775

1726

1684

1634

1588

1538

1492

1448

1398

ON ON

1843

1798

1753

1710

1666

1618

1574

1526

1481

1432

DM96SE 

0805C

OFF OFF

1012

937

861

801

722

630

552

485

420

353

ON OFF

1836

1787

1746

1699

1653

1607

1561

1514

1471

1419

OFF ON

1836

1787

1746

1699

1653

1607

1561

1514

1471

1419

ON ON

2215

2171

2137

2098

2060

2022

1986

1948

1908

1869

DM96SE 

1005C

OFF OFF

1012

940

863

800

715

627

561

496

437

374

ON OFF

1826

1783

1730

1685

1642

1596

1548

1504

1455

1406

OFF ON

1602

1556

1510

1460

1411

1372

1315

1261

1207

1156

ON ON

2225

2180

2141

2105

2070

2033

1996

1957

1923

1883

DM96SE 

1205D

OFF OFF

1121

1018

933

839

762

671

592

519

447

371

ON OFF

1969

1913

1862

1807

1756

1705

1647

1599

1544

1481

OFF ON

1865

1812

1755

1692

1638

1587

1527

1476

1411

1351

ON ON

2268

2214

2173

2117

2068

2022

1978

1924

1874

1832

¹ at 0.5" ESP

Notes

• 

CFM in chart is without filter(s).  Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires 

 

two return filters, this chart assumes both filters are installed.

• 

All furnaces ship as high-speed cooling and medium-speed heating. Installer must adjust blower cooling & heating speed as needed.

• 

For most jobs, about 400 CFM per ton when cooling is desirable.

• 

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

• 

This chart is for information only.  For satisfactory operation, external static pressure should not exceed value shown on the rating plate. 

 

The shaded area indicates ranges in excess of maximum static pressure allowed when heating.

• 

The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately 

 

the same temperature rise at a particular CFM, while ESP at the CFM will be lower.

DM96SE Airflow Data  

Summary of Contents for DM96SE

Page 1: ...d Features Cabinet Features Heavy duty stainless steel tubular heat exchanger Stainless steel secondary heat exchanger Single stage gas valve Durable Silicon Nitride igniter Multi speed blower motor S...

Page 2: ...Downflow Horizontal A Initial Release B 1st Revision AFUE 97 97 98 AFUE 92 92 AFUE NOx 96 96 AFUE N Low Nox 40ng J Gas Valve Cabinet Width M Modulating A 14 V Two Stage S Single Stage B 17 C 21 Motor...

Page 3: ...h 1000 above 4500 altitude DOE AFUE based upon Isolated Combustion System ICS Vent and combustion air diameters may vary depending upon vent length Refer to the latest editions of the National Fuel Ga...

Page 4: ...rtified NO NO NO NO NO Natural Gas BTU h for altitudes 0 4500 above sea level reduce input rating by 4 for each 1000 above 4500 altitude DOE AFUE based upon Isolated Combustion System ICS Vent and com...

Page 5: ...0 19 20 5 9 19 34 19 B C 23 2 1 2 2 6 5 9 19 23 24 31 A 21 2 14 23 1 1 287 8 2 1 2 2 2 6 1 26 23 Folded Flanges 22 Unfolded Flanges D Unfolded Flanges E Folded Flanges Air Discharge Air Discharge LEFT...

Page 6: ...r Drain Trap Holes Low Voltage Electrical Outlet Air Discharge Air Discharge Folded Flanges B 18 Minimum Clearances to Combustible Materials Position Sides Rear Front Bottom Flue Top Downflow 0 0 3 NC...

Page 7: ...N A 800 N A 715 N A 627 561 496 ON OFF 1826 49 1783 50 1730 51 1685 53 1642 54 1596 1548 1504 ON ON 1465 N A 1402 N A 1360 N A 1306 N A 1250 N A 1197 1138 1073 OFF ON 1602 55 1556 57 1510 59 1460 N A...

Page 8: ...ON 2215 2171 2137 2098 2060 2022 1986 1948 1908 1869 DM96SE 1005C OFF OFF 1012 940 863 800 715 627 561 496 437 374 ON OFF 1826 1783 1730 1685 1642 1596 1548 1504 1455 1406 OFF ON 1602 1556 1510 1460 1...

Page 9: ...0 935 861 785 721 631 553 483 423 350 ON OFF ON 1010 935 861 785 721 631 553 483 423 350 ON ON ON 1010 935 861 785 721 631 553 483 423 350 ON OFF OFF 1621 1570 1521 1467 1414 1378 1327 1274 1221 1167...

Page 10: ...205D OFF OFF 1296 N A 1190 N A 1076 N A 960 N A 839 N A 760 653 559 ON OFF 1917 56 1843 58 1759 61 1686 63 1600 67 1513 1420 1348 ON ON 1611 66 1521 70 1433 74 1347 N A 1246 N A 1145 1044 953 OFF ON 2...

Page 11: ...OFF ON 2230 2176 2125 2086 2038 1999 1958 1917 1880 1829 DC96SE 1205D OFF OFF 1296 1190 1076 960 839 760 653 559 452 351 ON OFF 1917 1843 1759 1686 1600 1513 1420 1348 1258 1173 ON ON 2011 1936 1858...

Page 12: ...266 224 190 OFF ON ON 760 686 613 542 459 376 310 266 224 190 ON OFF ON 760 686 613 542 459 376 310 266 224 190 ON ON ON 760 686 613 542 459 376 310 266 224 190 ON OFF OFF 1390 1342 1292 1254 1201 11...

Page 13: ...T BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 80...

Page 14: ...OWER PRESSURE SWITCH RD WH BURNER COMPARTMENT BLOWER COMPARTMENT NO YL CONTROL PRIMARY LIMIT AUTO RESET BL PU MANUAL RESET ROLLOUT LIMIT CONTROL S RD OR PK BK WH WH BLOWER INDUCED DRAFT AUXILIARY LIMI...

Page 15: ...ion Kits Notes Indicates available for this model Indicates 9 001 to 11 000 altitude Indicates 7 001 to 9 000 altitude Indicates 7 001 to 11 000 altitude All installations above 7 000 require a pressu...

Page 16: ...16 www daikincomfort com SS DM96SE Our continuing commitment to quality products may mean a change in specifications without notice 2021 Houston Texas Notes...

Reviews: