background image

21

be  established  within  three  (3)  consecutive  ignition 

attempts.  If flame is not established within the seven (7) 

second trial for ignition, the gas valve is de-energized, 

15 second inter-purge cycle is completed, and ignition 

is reattempted.  The control will repeat this routine three 

times if a measurable combustion is not established.  The 

control will then shut off the induced draft blower and go 

into a lockout state.

If flame is established but lost, the control will energize 

the circulator blower at the heat speed and then begin a 

new ignition sequence.  If flame is established then lost 

on subsequent attempts, the control will recycle for four 

(4)  consecutive  ignition  attempts  (five  attempts  total) 

before locking out.

The diagnostic fault code is 1 flash for a lockout due to 

failed ignition attempts or flame dropouts.  The integrated 

control will automatically reset after one hour, or it can be 

reset by removing the thermostat signal or disconnecting 

the electrical 

power supply for over five seconds. If the 

diagnostic  LED indicates  an external lockout, perform 

the following checks:

 • 

Check the supply and manifold pressures

 • 

Check the gas orifices for debris

 • 

Check gas valve for proper operation

 • 

Check secondary limit

A dirty filter, excessive duct static, insufficient air 

flow, a faulty limit, or a failed circulator blower can 

cause this limit to open.  Check filters, total external 

duct static, circulator blower motor, blower motor 

speed  tap  (see  wiring  diagram),  and  limit.   An 

interruption  in  electrical  power  during  a  heating 

cycle may also cause the auxiliary limit to open.  

The automatic reset secondary limit is located on 

top of the circulator blower assembly. 

 • 

Check rollout limit

If the burner flames are not properly drawn into 

the  heat  exchanger,  the  flame  rollout  protection 

device will open.  Possible causes are restricted 

or  blocked  flue  passages,  blocked  or  cracked 

heat exchanger, a failed induced draft blower, or 

insufficient combustion air. The rollout protection 

device is a manual reset limit located on the burner 

bracket.  The cause of the flame rollout must be 

determined and corrected before resetting the limit. 

 • 

Check flame sensor

A drop in flame signal can be caused by nearly 

invisible coating on the sensor.  Remove the sensor 

and carefully clean with steel wool.

 • 

Check wiring

Check wiring for opens/shorts and miswiring.

 Important:

  If you have to frequently reset your gas/

electric package unit, it means that a problem exists 

that should be corrected.  Contact a qualified servicer 

for further information.

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty 

pressure switch, faulty wiring, a disconnected or damaged 

hose,  a  blocked  or  restricted  flue,  or  a  faulty  induced 

draft blower.

If the control senses an open pressure switch during the 

pre-purge  cycle,  the  induced  draft  blower  only  will  be 

energized.  If the pressure switch opens after ignition 

has begun the gas valve is de-energized, the circulator 

blower heat off cycle begins, and the induced draft blower 

remains on.  The diagnostic fault code is two flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty 

pressure switch or faulty wiring.  If the control encounters 

a pressure switch stuck closed, the induced draft blower 

remains off.  The diagnostic LED code for this fault is 

three (3) flashes.

Open Thermal Protection Device

If  the  primary  limit  switch  opens,  the  gas  valve  is 

immediately  de-energized,  the  induced  draft  and  air 

circulating  blowers  are  energized.   The  induced  draft   

and air circulator blowers remain energized until the limit 

switch recloses.  The diagnostic fault code for an open 

limit is four (4) flashes.

A  primary  limit  will  open  due  to  excessive  supply  air 

temperatures.  This can be caused by a dirty filter, excessive 

duct static, insufficient air flow, or a faulty limit.  Check 

filters, total external duct static, blower motor, blower motor 

speed 

tap (see wiring diagram), and limit. This limit will 

automatically reset once the temperature falls below a 

preset level.

Primary Limit

A  primary  limit  will  open  due  to  excessive  supply  air 

temperatures.  This  can  be  caused  by  a  dirty  filter, 

excessive duct static, insufficient air flow, or a faulty limit. 

Check  filters,  total  external  duct  static,  blower  motor, 

blower motor speed tap (see wiring diagram), and limit. 

This limit will automatically reset once the temperature 

falls below a preset level.

Auxiliary/Secondary Limit

A dirty filter, excessive duct static, insufficient air flow, a 

faulty limit, or a failed circulator blower can cause this limit 

to open.  Check filters, total external duct static, circulator 

blower  motor,  blower  motor  speed  tap  (see  wiring 

diagram), and limit. An interruption in electrical power 

during a heating cycle may also cause the auxiliary limit 

to open. The automatic reset secondary limit is located 

on top of the circulator blower assembly.

Rollout Limit

If the burner flames are not properly drawn into the heat 

exchanger, the flame rollout protection device will open.  

Possible causes are restricted or blocked flue passages, 

blocked  or  cracked  heat  exchanger,  a  failed  induced 

draft blower, or insufficient combustion air. The rollout 

protection device is a manual reset limit located on the 

burner bracket.  The cause of the flame rollout must be 

determined and corrected before resetting the limit.

Flame Detected with Gas Valve Closed

If flame is detected with the gas valve de-energized, the 

combustion and air circulator blowers are energized. The 

diagnostic fault code is five (5) flashes for this condition. 

The control can be reset by removing the power supply 

to the unit or it will automatically reset after one hour. 

Miswiring is the probable cause for this fault.

Summary of Contents for DP3G Series

Page 1: ...HIS MANUAL OR ATTEMPTING TO INSTALL ADJUST SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH INSTAL...

Page 2: ...ESSURE MEASUREMENT 15 GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT 16 COOLING STARTUP 19 CHECKING SUBCOOLING 19 CHECKING SUPERHEAT 19 TROUBLESHOOTING 20 IGNITION CONTROL ERROR CODES 20 ABNORMAL OP...

Page 3: ...R DEATH DO NOT USE THIS U NIT IF ANY PART HAS BEEN UNDER WATER IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM A ND A NY GAS CONTRO...

Page 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Page 5: ...agent should be made in writing immediately Carefully inspect the unit for damage including damage to the cabinetry Any bolts or screws which may have loosened in transit must be retightened In the e...

Page 6: ...If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked by snow or debris In some climates or locations it may be necessary to elevate the unit to avo...

Page 7: ...e rigging unit center of gravity will cause condenser end to be lower than supply air end Unit should be lifted by the 4 holes located at the base frame corners Lifting cables should be attached to th...

Page 8: ...40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0...

Page 9: ...PIPE OR TUBING LENGTH FEET Table 3 Propane Gas Pipe Sizing Gas Piping Checks CAUTION TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED R EGARDING G...

Page 10: ...E A WARNING DEVICE IS REQUIRED DUE TO PROPANE GAS IS HEAVIER THAN A IR AND ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE EXCEP...

Page 11: ...208V reconnect the transformer primary lead as shown on the unit wiring diagram NOTE 5 ton models The induced draft blower on some models is equipped with a low speed 240V lead blue and a low speed 20...

Page 12: ...dimensions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transm...

Page 13: ...TE The igniter produces a very intense electrical spark that ignites the gas 4 Main burners light and control detects presence of flame 5 The 30 second HEAT FAN ON delay time begins after the main bur...

Page 14: ...e compressor and outdoor fan are energized at low stage If the thermostat call is for high stage cooling the compressor and outdoor fan are energized at high stage 2 Approximately seven seconds later...

Page 15: ...ust Regulator Vent Outlet Pressure Boss White Rodgers Model 36G54 Two Stage Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate NOTE Use adapt...

Page 16: ...all electrical power and gas supply to the system 10 Remove the manometer hose from the hose barb fitting or inlet pressure boss 11 Replace inlet pressure tap White Rodgers 36J22 or 36G54 valve Turn i...

Page 17: ...3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High or Single Stage 9 7 10 3 w c 10 0 w c Manifold Gas Pressure Gas Natural LP 10 Turn OFF all electrical power and gas supply to the system 11 Remov...

Page 18: ...together NOTE Both readings may be taken simultaneously and read directly on the manometer if so desired 4 Consult proper table for quantity of air If the external static pressure exceeds the minimum...

Page 19: ...nit comes factory charged but this charge is based on 325 CFM per ton and minimum ESP per AHRI test conditions generally between 15 28 ESP When air quantity or ESP is different than above the refriger...

Page 20: ...lower the subcooling NOTE Do NOT adjust the charge based on suction pressure unless there is a gross undercharge 4 Disconnect manifold set installation is complete Model Superhe at 2 F Subcooli ng 1 F...

Page 21: ...senses an open pressure switch during the pre purge cycle the induced draft blower only will be energized If the pressure switch opens after ignition has begun the gas valve is de energized the circu...

Page 22: ...t the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air...

Page 23: ...ar prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit which is held by two screws If yo...

Page 24: ...Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansion Valve Evaporator Coil Transformer FUNCTIONAL PARTS Functional Parts List General Information 1 Refer to the...

Page 25: ...1 206 879 259 DP3GM2406041 Rise Range 30 60 E S P T1 HEATING SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SPEED CFM WATTS RISE CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS...

Page 26: ...635 91 X 1030 221 60 1175 300 52 1358 354 1365 440 0 4 570 98 X 985 233 X 1140 303 54 1319 361 1335 440 0 5 505 107 X 940 234 X 1100 311 56 1277 366 1295 456 0 6 450 115 X 895 242 X 1055 319 58 1232 3...

Page 27: ...1740 658 0 3 940 173 X 1270 318 48 1305 343 47 1754 696 1695 661 0 4 880 181 X 1220 327 50 1260 353 49 1706 702 1640 679 0 5 825 189 X 1160 336 53 1200 359 51 1665 710 1595 675 0 6 760 204 X 1115 342...

Page 28: ...331 55 1318 302 1955 779 2015 850 0 4 985 194 59 1350 341 57 1268 313 1913 785 1972 858 0 5 905 199 64 1295 351 59 1217 326 1871 796 1930 864 0 6 840 215 X 1235 359 62 1163 341 1828 803 1888 875 0 7...

Page 29: ...en 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only 0 15 22 45 52 0 29...

Page 30: ...Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Signal Refer to Abnormal Heating or Cooling Operation Sections...

Page 31: ...2 Large Model Duct Openings Supply Return W H W H GPD1424060M41 16 16 16 16 GPD1430080M41 16 16 16 16 GPD1436080M41 16 16 16 16 GPD1442100M41 16 18 16 18 GPD1448100M41 16 18 16 18 Model Unit Dimensio...

Page 32: ...ram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMA...

Page 33: ...2 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS 4 FOR DIFFERENT THAN FACTORY SPEED TAP CHANGE COOLING SPE...

Page 34: ...RD WH WH YL YL SEE NOTE 7 YL WH BL BL BL BR BR RD OR BL BL BL BL RD RD RD RD PU WH OR RD YL YL Y Y2 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12...

Page 35: ...BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL USE COPPER CONDUCTOR ONLY 2 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 3 CRANKCASE HEATER NOT...

Page 36: ...S T1 LOW INDUCER L2 BK YL RD GR SEE NOTE 3 EM 208 PU YL PU BK N G L T5 T4 T3 T2 T1 240 3 TR 2 RD 24V C 1 YL BL 208 230 1 60 POWER SUPPLY GND C PU PU RD BK BR PU BK R S COMP C T2 T1 CC L2 L1 ALS CM LPS...

Page 37: ...TAGE P1 INTEGRATED IGNITION CONTROL CC CC COM HLI SEE NOTE 2 INTERGRATED IGNITION CONTROL F Y1 R C Y2 W2 W1 TO MICRO TO MICRO INTEGRATED IGNITION CONTROL L1 LO L2 L2 L2 L2 YL RD SOL ODF OUTDOOR FAN HP...

Page 38: ...U WH OR RD YL YL Y IGN FS FC PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 150 120 ECON 135 P1 F1 FUSE 3 AMP MAX P3 GR YL WH YL YL COMPRESSOR COOL SCREW...

Page 39: ...E SENSED OUTPUT DELAY OPEN LIMIT SWITCH COMPRESSOR WITHOUT INDUCER ON PRESSURE SWITCH CLOSED PRESSURE SWITCH OPEN AUX LIMIT OPEN ROLLOUT SWITCH OPEN SWITCH IGNITION FAILURE NORMAL OPERATION NO POWER O...

Page 40: ...RD RD RD RD PU WH OR RD PLF YL YL YL GR PU YL Y Y2 Y1 1 2 3 IGN FS RCCF PU BL BR PU RD RD YL YL RS PU PU BL VM PU L2 UNUSED HEAT FS L1 DI 1 3 6 5 2 4 10 7 9 12 8 11 150 120 ECON 135 P1 GR RD YL WH YL...

Page 41: ...CK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 3 CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS 4 FOR DIFFERENT THAN FACTORY SPEED TAP CHANGE COOLING SPEED AT MOTOR T4 AND T5 TERMINALS CHANGE HEATIN...

Page 42: ...BK RD GR SEE NOTE 3 EM 208 PU YL PU BK N G L T5 T4 T3 T2 T1 240 3 TR 2 RD 24V C 1 YL BL 208 230 3 60 POWER SUPPLY GND C PU PU RD BK BR PU BK T2 T3 COMP T1 T2 T1 CC L2 L1 ALS CM LPS HPS PARK BK PU SEE...

Page 43: ...HI M RS PS LS ALS TR EM VM L2 T2 208 230 3 60 CM L1 T2 T1 T3 COMP T1 SUPPLY VOLTAGE P1 CC CC COM HLI SEE NOTE 2 INTERGRATED IGNITION CONTROL F Y1 R C Y2 W2 W1 TO MICRO TO MICRO LO RD SOL ODF OUTDOOR F...

Page 44: ...ed Servicer Only Your package unit should be inspected by a qualified installer or service agency at least twice every year This check should be performed before the heating and cooling seasons begin...

Page 45: ...tural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1and L2Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressu...

Page 46: ...46 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 47: ...47 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 48: ...19001 Kermier Road Waller TX 77484 www daikincomfort com 2022 CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daikinco...

Reviews: