10
REPLACING THE CONTROL BOARD (2, 3, & 4 TON ONLY)
WARNING
HIGH VOLTAGE
DISCONNECT ALL POWER BEFORE SERVICING
OR INSTALLING THIS UNIT. MULTIPLE POWER
SOURCES MAY BE PRESENT. FAILURE TO DO SO
MAY CAUSE PROPERTY DAMAGE, PERSONAL IN-
JURY OR DEATH.
CAUTION
WHEN REPLACING THE CONTROL BOARD, DO NOT TOUCH THE
HATCHED AREAS. BEFORE INSTALLING THE NEW CONTROL
BOARD, BE SURE TO WIPE THE GREASE OFF THE REFRIGERANT
TUBING. EXERCISE CAUTION TO NOT DAMAGE THE ELECTRICAL
CONNECTIONS. DISCONNECT AS NEEDED.
Uninstall the control board
When uninstalling the main control board, remove the
screws holding the cover in place. If board replacement is
attempted without following proper uninstallation procedure,
the refrigerant piping might be damaged. Always replace the
grease with new grease on heat sink used for cooling. Not
replacing grease may result in insufficient cooling and may
damage the control board.
1.
Remove the fixing screw A.
2. Lift the cover and open it in the direction shown in the
figure.
3.
Remove fixing screws B affixing the sheet metal plate.
4. Carefully slide the sheet metal plate with the control
board behind the refrigerant tubing as shown.
Fixing
screw A
Cover
Refrigerant Tubing
Heat sink for cooling
fixing screws B
Install the control board
When working on a service port, ensure that no refrigerant
and/or compressor oil is sprayed onto the control board.
This could damage the board’s functionality.
1. Wipe the stale grease completely from the installed pip-
ing. If you reinstall the control board, make sure to wipe
clean the heat sink on the board. Coat the surface with
the standard quantity of the specified new grease.
2.
Carefully slide the sheet metal plate back in and fix the
screws B.
3. Do not apply force to the parts on the control board.
Hold the control board plate NOT the control board.
4. Ensure that the liquid tube does not come in contact with
any part of the control board assembly.
5.
Gently fit the tube in the heat sink troughs. Ensure there
is good contact.
6.
Close the cover, slide it downwards, fix it with the nails
(two nails) and tighten fixing screws A so that the piping
is tightly connected.
Use the grease that
is provided with the
service parts
.20
.20
Make sure
that you are
coating
evenly
Tightening torque:
14.1±1.7 lbf-in
Tighten with a driver until
the position where a
tightening torque increases
suddenly.
Then extra-tighten by
30° to 40°
Nail
Nail
screw A