CKT04 ADDENDUM
103
Set 7-Segment Mode Display to Pump Down
Please follow the following sequence to enter PUMP DOWN
to accumulate the refrigerant to outdoor unit.
Do not operate COOL ON mode to enter PUMP DOWN.
Before starting the PUMP DOWN operation, change indoor
fan trim, delay and profile back to default and stop electric
heater and gas furnace. Remove if no trim feature. In this
operation, the gas and liquid service valve should be opened.
1. 1. Set 7-segment display to SCREEN 4 (SETTING MODE
2) Setting No. 8 and change the display from “-01” to
“-00”. System will then automatically start PUMP DOWN
operation. For information on how to set 7-segment
display, see the section SETTING THE MODE DISPLAY
in this manual.
S
ET
T
HERMOSTAT
TO
C
HECK
SYSTEM STATUS
1. Follow the sequence 1. to 5. of
S
ET
T
HERMOSTAT
TO
A
DJUST
I
NDOOR
A
IR
CFM
TRIM
.
2. Select STATUS.
3. Follow screen for System Status.
TS
MD
CRM
RAD
Requested and Actual percentage Demand
(Requested Demand, Actual cooling provided)
RAF
(Requested CFM, Actual CFM)
ATOF*
Outdoor Air Temperature, Outdoor Fan speed
(OD air temperature, OD Fan RPM)
DCT
Dis charge Temperature, Outdoor Coil Temperature
DLT
Outdoor Liquid Temperature
PSDST**
*Only for DX20VC0**1AC or later revision. ATPRM is shown in
DX20VC0**AA/AB revision.
** Only for DX20VC0**1AC or later revision. PSD is shown in
DX20VC0**1AA/AB revision.
F
2. Approximately one minute later, the compressor should
start operating. Check the amperage at the compressor
wiring to see the compressor operation status. Unit
displays error code E11 (System Verification Test) once
the PUMP DOWN operation starts.
3. Close liquid service valve approximately two minutes after
compressor has come on.
4. Compressor will come to a stop automatically. Close
the gas service valve immediately after the compressor
stops. After completion of PUMP DOWN, unit shows
error code “E11”.
NOTE
: Refrigerant cannot be collected to the outdoor unit
completely if the system is overcharged or if there is a delay
in closing the liquid service valve and gas service valve.
Evacuate the left over refrigerant from the system using a
recovery machine.