71
TROUBLESHOOTING-OUTDOOR UNIT
Re-Writing Shared Data to Outdoor Unit
Using Memory Card
Check Troubleshooting codes to determine the need to flash
shared data to outdoor unit. Follow the below procedure to
flash shared data.
Procedure to Flash Shared Data to Out
-
door Unit Using Memory Card
1. Turn the power OFF to the outdoor unit.
2. Disconnect the Climate Talk (CT) connector from the
outdoor unit.
3. Insert the memory card on the outdoor unit.
4. Turn the power ON to the outdoor unit.
5.
Verify that H1P (red LED) flashes twice. This step con
-
firms that the data has been transferred from the mem
-
ory card to the outdoor unit.
6. Turn the power OFF to the outdoor unit.
7. Remove the memory card from the unit.
8. Connect the Climate Talk (CT) connector to the outdoor
unit.
9. Turn the power ON to the outdoor unit.
10. Continue the operation of the unit as desired.
NOTE
:
1. If there is an error E11 on the 7-segment display of the
Outdoor unit after step 11, run the SYSTEM VERIFICA-
TION TEST on the Outdoor unit using the thermostat
menu.
•
AC - Menu → Air Conditioner → Equip Test → Sys
-
tem Verification Test → ON
•
HP - Menu → Heat Pump → Equip Test → System
Verification Test → ON
2.
The control boards for different 20 SEER OD units (2T,
3T, 4T, 5T) are different. Below are the names of the
connectors for quick identification.
• Memory Chip connector - X52A (white - 12 pin con-
nector)
• Climate Talk connector - X851A (green - 9 pin con-
nector)
• Red LED - H1P
Climate Talk
Connector
(X851A)
Iden
tificati
on of
c
onne
ct
ors on 20 SEER OD Con
t
rol Bo
a
rd