5
ACCESSORIES
DV*PEC
For heater kit installation, it is important to set the capacity of the electric heater at Set-up menu on thermostat and DIP switch on
indoor unit control board. For more information, please see indoor unit I/O manual.
*Revision level that may or may not be designated.
NOTE: Airflow selection should meet the minimum requirements as mentioned in the air handler installation instructions.
+
For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to a speed tap corresponding to 1170 cfm.
++
For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to a speed tap corresponding to 1240 cfm.
ACCESSORIES
MODELS
HK
SX
03
X
C
HK
SX
05
X
C
HK
SX
06
X
C
HK
SX
08
X
C
HK
SX
10
X
C
HK
S
C
05X
C
HK
S
C
08X
C
HK
S
C
10X
C
HK
SC
15
X
A
HK
SC
15
X
B
HK
S
C
15X
F
HK
SC
19
C
A
HK
S
C
19C
B
HK
S
C
20DA
HK
SC
20
DB
HK
S
C
20X
F
HK
SC
25
DC
DV25PECB14A*
X
X
X
X
X
X
X
X
DV37PECC14A*
X
X
X
X
X
X
X
X
X
X
X
X
DV59PECD14A*
X
X
X
X
X
X
X
X
X
X
X
X
X
DV61PECD14A*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Heater Kit
Selection
DV25PECB14A*
DV37P
DV59P+
DV61PECD14A*
S-9
S-10
S-11
S-12
No hea ter
-
-
-
-
OFF
OFF
OFF
OFF
Firs t
3
5
5
5
ON
ON
ON
ON
Second
5
6
6
6
ON
ON
ON
OFF
Thi rd
6
8
8
8
ON
ON
OFF
ON
Fourth
8
10
10
10
ON
ON
OFF
OFF
Fifth
10
15
15
15
ON
OFF
ON
ON
Sixth
X
19
20
20
ON
OFF
ON
OFF
Seventh
X
X
X
25
ON
OFF
OFF
ON
VALID SWITCH SETTINGS
Heater kW
Dip Switch Setting Indoor PCB DS Bank 3