Technical specifications
(1)
Electrical specifications
(1) Refer to the engineering data book for the complete list of specifications.
General EWWQ
98
113
128
147
162
177
192
Dimensions HxWxD
(mm)
1200x600x1200
1800x600x1200
Machine weight
(kg)
620
650
680
930
960
990
1020
Connections
• water inlet
2x 2x G1-1/2
3x 3x G1-1/2
• water outlet
2x 2x G1-1/2
3x 3x G1-1/2
Compressor
98
113
128
147
162
177
192
Model
4x JT236DJ-Y1
2x JT236DJ-Y1 +
2x JT315DJ-Y1
4x JT315DJ-Y1
6x JT236DJ-Y1
4x JT236DJ-Y1 +
2x JT315DJ-Y1
2x JT236DJ-Y1 +
4x JT315DJ-Y1
6x JT236DJ-Y1
Speed
2900
2900
Oil type
FVC68D
FVC68D
Oil charge volume
(l)
4x 3.0
6x 3.0
Refrigerant type
R410A
R410A
Refrigerant charge
(kg)
2x4.6
4.6+5.6
2x5.6
3x4.6
2x4.6+5.6
4.6+2x5.6
3x5.6
Evaporator
049
064
079
094
109
124
139
Type
Brazed plate heat exchanger
Nom Water volume
(l/min)
205
311
417
523
629
735
841
Water flow range
(l/min)
202 - 493
262 - 642
304 - 745
333 - 814
393 - 963
435 - 1066
456 - 1118
Condenser
049
064
079
094
109
124
139
Type
Brazed plate heat exchanger
Water flow range
(l/min)
157 - 629
205 - 819
237 - 948
260 - 1038
307 - 1293
339 - 1357
355 - 1422
General EWWQ
98
113
128
147
162
177
192
Power Supply
• Phase
3N~
3N~
• Frequency
(Hz)
50
50
• Voltage
(V)
400
400
• Voltage tolerance
(%)
±10
±10
Unit
• Nominal running
current
(A)
43
52
61
64
73
82
91
• Maximum running
current
(A)
65
73
81
97
105
113
121
• Recommended fuses
(A)
3x80
3x80
3x100
3x100
3x125
3x125
3x125
Compressors
• Phase
3N~
3N~
• Frequency
(Hz)
50
50
• Voltage
(V)
400
400
• Nominal running
current
(A)
10.5
10.5/15
15
10.5
10.5/15
10.5/15
15