Installation manual
43
E(D/B)(H/L)Q011~016BB
Unit for air to water heat pump system
4PW67904-1 – 01.2011
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting
"[1] Weather
dependent set point" on page 32
) is selected.
■
[d-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
Target water temperature
T
A
Outdoor temperature
R Range
L Local shift value
[1-00]~[1-04] Applicable field settings of the weather dependent set
point [1].
[E] Unit information readout
■
[E-00] Readout of the software version (example: 23)
■
[E-01] Readout of the EEPROM version (example: 23)
■
[E-02] Readout of the unit model identification (example: 11)
■
[E-03] Readout of the liquid refrigerant temperature
■
[E-04] Readout of the inlet water temperature
[F] Option setup
Pump operation
The pump operation field setting apply to the pump operation logic
only when DIP switch SS2-3 is OFF.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4-02] or if the
outdoor temperature drops below the value set by [F-01]. When the
pump operation is enabled, the pump operation is possible at all
outdoor temperatures. Refer to
"10.3. Pump operation configuration"
on page 29
.
■
[F-00] Pump operation: specifies wether the pump operation
function is enabled (1) or disabled (0).
Space cooling permission
■
[F-01] Space cooling permission temperature: defines the
outdoor temperature below which space cooling is turned off.
Bottom plate heater control
Applies only to installation with an E(D/B)LQ unit or in case the option
bottom plate heater kit is installed.
■
[F-02] Bottom plate heater ON temperature: defines the
outdoor temperature below which the bottom plate heater will
be activated in order to prevent ice build-up in the bottom
plate at lower outdoor temperatures.
■
[F-03]
Bottom plate heater hysteresis: defines the
temperature difference between bottom plate heater ON
temperature and the bottom plate heater OFF temperature.
Bottom plate heater
T
A
Outdoor temperature
Functionality of X14A
■
[F-04] Functionality of X14A: specifies if the logic of X14A
follows the output signal for the solar kit model (EKSOLHW)
(0) or if the logic of X14A follows the output for the bottom
plate heater (1).
[d-03]
Outdoor temperature range
(T
A
)
Local shift value
0
—
—
1
–2°C~2°C
2
2
4
3
–4°C~4°C
2
4
4
NOTICE
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated after
looping through the field setting first codes again only.
T
A
T
t
[1-03]
[1-00]
0
°
C
[1-01]
[1-02]
L
R
INFORMATION
This function is only valid for EB units when space
cooling is selected.
CAUTION
The bottom plate heater is controlled via X14A. Make sure
[F-04] is correctly set.
INFORMATION
Independent from field setting [F-04], the contact X3-X4
(EKRP1HB) follows the logic of the output signal for the
solar kit model (EKSOLHW). See figure below for the
schematic location of this contact.
T
A
[F-02]
[F-03]
ON
OFF
YC Y1 Y2 Y3 Y4
X1
X2
X3
X4
OFF ON
X2M
SS1
X1M