8.  Locate 9-pin plug in unit.
9.  Connect the plug to the maiting 9-pin plug attached to heater kit 

(Figure 4).

10.  Install blower door and horizontal supply cover if it was removed.
11.  Reconnect power.
12. Set up a required airflow - CFM for your unit with electic heater 

by selecting a proper speed tap. For details see Air Flow Ad-

justment chapter in IOD-1032 for DRC and DRH models or in 

IOD-1043 for DBC and DBG models.

•  Refer to Air Flow for Electric Heat table in this document to identi-

fy minimum required CFM for your unit with specific heater model.

•  Refer to Appendix A - Blower Performance Tables for speed tap 

selection in IOD-1032 for DRC and DRH models or in IOD-1043 

for DBC and DBH models.

13. Close control box door.
14. Reconnect power to the unit.
15. Test unit to ensure it is functioning properly.
16. Place Heater wiring diagram beside unit diagram.

UNITS

HEATER KIT 

MODEL NUMBER kW

MINIMUM 

SCFM

EH*-*S05

5

EH*-*S10

10

EH*-*S15

15

EH*-*S05

5

EH*-*S10

10

EH*-*S15

15

EH*-*S18

18

EH*-*S20

20

EH*-*S05

5

EH*-*S10

10

EH*-*S15

15

EH*-*S20

20

EH*-*S05

5

EH*-*S10

10

EH*-*S15

15

EH*-*S20

20

1950

AIR FLOW FOR ELECTRIC HEAT

DRC060, DRH060, 

DBC060, DBH060

DRC036, DRH036, 

DBC036, DBH036

DRC048, DRH048, 

DBC048, DBH048

975

1300

1625

DRC072, DRH072, 

DBC072, DBH072

            HEATER KIT MODEL NUMBER NOMENCLATURE 

E

H

*

-

*

S

15

1

2

3

-

4

5

6, 7

Electric

Heater

Heater Type

X  

Staged

SCR (modulating)

Voltage

1

208-230/1/60

Single phase 60 Hz

3

208-230/3/60

Three phase 60 Hz

4

460/3/60

Three phase 60 Hz

7

575/3/60

Three phase 60 Hz

Chassis

S

Small

M

Medium

L

Large

Kilowatt

5

5 kW

10

10 kW

15

15 kW

18

18 KW

20

20 kW

30

30 kW

Summary of Contents for EHS Series

Page 1: ...flict between existing practices and the content of this manual the precautions listed here take precedence Description These installation instructions supplement the electric heater kits for installation in the following models DRC036 DRC048 DRC060 DRC072 DRH036 DRH048 DRH060 DRH072 DBC036 DBC048 DBC060 DBC072 DBH036 DBH048 DBH060 DBH072 These instructions should be used only as a supplement to i...

Page 2: ...re 4 A HEATING ELEMENT SCREWS FROM UNIT FIGURE 3 BACK RODS OF HEATER KIT TO BE PLACED IN SLOTS OF RETAINER BRACKET DETAIL A 7 Connect power to kit Remove power cable from the box Connect leads to breakers with one lead for each power leg Route all leads through the blower deck and into the control box as shown in Figure 4 Connect the leads to the single point black with the far left lug L1 the mid...

Page 3: ... and DBH models 13 Close control box door 14 Reconnect power to the unit 15 Test unit to ensure it is functioning properly 16 Place Heater wiring diagram beside unit diagram UNITS HEATER KIT MODEL NUMBER kW MINIMUM SCFM EH S05 5 EH S10 10 EH S15 15 EH S05 5 EH S10 10 EH S15 15 EH S18 18 EH S20 20 EH S05 5 EH S10 10 EH S15 15 EH S20 20 EH S05 5 EH S10 10 EH S15 15 EH S20 20 1950 AIR FLOW FOR ELECTR...

Page 4: ...d forgiving to operate We use qual ity materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www daikincomfort com for information on Products Warranties Customer Services Parts Contractor Program and Training Financing Options 2019 CUSTOMER FEEDBACK Daikin is very interested in all product comments ...