7 Installation
Installer reference guide
32
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12
>250
>300
>250
(mm)
a
b
c
4×
a
Maximum snowfall height
b
EKFT008D option kit
c
Anti-vibration rubber (field supply)
7.3.4
To install the outdoor unit
CAUTION
Do NOT remove the protective cardboard before the unit is
installed properly.
1
Lift the outdoor unit as described in
"3.2.2 To handle the
outdoor unit" on page 7
.
2
Install the outdoor unit as follows:
▪ (1) Put the unit into position (using the sling to the left and
the handle to the right).
▪ (2) Remove the sling (by pulling 1 side of the sling).
▪ (3) Fix the unit.
2×
3
2
1
a
a
a
Air outlet
NOTICE
Properly align the unit. Make sure the backside of the unit
does NOT protrude.
3
Remove the protective cardboard and instruction sheet.
a
b
a
Protective cardboard
b
Instruction sheet
7.3.5
To provide drainage
▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
▪ Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
NOTICE
If the drain holes of the outdoor unit are blocked up,
provide space of at least 300 mm below the outdoor unit.
▪
Drain pan.
You can use the drain pan option (EKDP008D) to
gather the drain water. For the complete installation instructions,
see the installation manual of the drain pan. In short, the drain pan
must be installed level (with a tolerance of 1° at all sides) and as
follows: