background image

Operation manual

5

EKHBH/X008BA

Indoor unit for air to water heat pump system and options

4PW54184-1

Setting up the controller

After initial installation, the user can set the clock and day of the
week.

The controller is equipped with a schedule timer that enables the
user to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.

Setting the clock

1

Hold down the 

pr

 button for 5 seconds.

The clock read-out and the day of week indicator start flashing.

2

Use the 

pi

 and 

pj

 buttons to adjust the clock.

Each time the 

pi

  or 

pj

  button is pressed, the time will

increase/decrease by 1 minute. Keeping the 

pi

  or 

pj

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

bi

 or 

bj

 button to adjust the day of the week.

Each time the 

bi

  or 

bj

  button is pressed the next or

previous day is displayed.

4

Press the 

<

 button to confirm the current set time and day of the

week.

To leave this procedure without saving, press the 

pr

 button.

If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.

Setting the schedule timer

To  set the schedule timer, refer to chapter 

"Programming and

consulting the schedule timer" on page 7

.

Description of the operation modes

Space heating operation (

h

)

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually (refer to

"Manual operation" on page 5

) or weather dependent (refer to

"Selecting weather dependent set point operation (only in heating
mode)" on page 6

).

Startup (

d

)

At the start of a heating operation, the pump is not started until a
certain refrigerant heat exchanger temperature is reached. This
guarantees correct startup of the heat pump. During startup, icon

d

 is displayed.

Defrost (

d

)

In space heating operation or heat pump domestic water heating
operation, freezing of the outdoor heat exchanger may occur due to
low outdoor temperature. If this risk occurs, the system goes into
defrost operation. It reverses the cycle and takes heat from the indoor
system to prevent freezing of the outdoor system. After a maximum
of 8 minutes of defrost operation, the system returns to space
heating operation.

Space cooling operation (

c

)

In this mode, cooling will be activated as required by the water
temperature set point.

Domestic water heating operation (

w

)

In this mode, the indoor unit will heat up the domestic hot water tank
by heat pump when the space heating/space cooling operation has
reached its temperature set point or heat pump domestic water
heating has a higher demand request than space side (depends on
dipswitch setting). When necessary and when allowed by the booster
heater schedule timer (refer to 

"Programming quiet mode, booster

heating or domestic water heating" on page 9

), the booster heater

provides auxiliary heating for the domestic hot water tank.

Powerful domestic water heating operation

In the case of urgent need of domestic hot water, the domestic hot
water temperature set point can be reached quickly by using the
booster heater. Powerful domestic water heating operation is forcing
the booster heater to operate until the domestic hot water
temperature set point is reached.

This function remains available in solar operation.

Quiet mode operation (

s

)

Quiet mode operation means that the outdoor unit works at reduced
capacity so that the sound produced by the outdoor unit drops. This
implies that the indoor heating and cooling capacity will also drop.
Beware of this when a certain level of heating is required indoors.

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 6

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space heating (

h

) and space cooling

(

c

)

1

Use the 

=

 button to select space heating (

h

) or space cooling

(

c

).

Icon 

h

 or 

c

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

  and 

bj

  buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"Field settings" on page 10

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to 

"Field

settings" on page 10

).

Temperature range for cooling: 5°C to 22°C

The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and vice
versa.

The space cooling temperature set point can only be
set manually (refer to 

"Manual operation" on page 5

).

Switching between space heating and space cooling
operation can only be done by pressing the 

=

button or by the external room thermostat.

Space cooling operation is not possible if the
installation is a "heating only" installation.

In order to provide domestic hot water throughout the
day, it is advised to keep the domestic water heating
operation on continuously.

The domestic hot water water temperature set point
can only be set manually (refer to 

"Manual operation"

on page 5

).

Any domestic water heating operation is impossible
when the domestic hot water tank is not installed.

When the 

w

 icon is blinking, the domestic hot water is

heating up by the solar kit option and not by the indoor
unit. Refer to installation manual of the EKSOLHW
solar kit.

Summary of Contents for EKHBH008BA

Page 1: ...OPERATION MANUAL EKHBH008BA EKHBX008BA Indoor unit for air to water heat pump system and options...

Page 2: ...water ERHQ or ERLQ heat pumps These units are designed for wall mounted indoor installation The units can be combined with Daikin fan coil units floor heating applications low temperature radiators D...

Page 3: ...stat connected to the indoor unit This will prevent excessive space heating and will stop the outdoor unit and the indoor circulation pump when the room temperature is above the thermostat set point N...

Page 4: ...eration mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic water heating The corresponding mod...

Page 5: ...E HEATING COOLING BUTTON This button allows manual switching between heating or cooling mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat th...

Page 6: ...ater provides auxiliary heating for the domestic hot water tank Powerful domestic water heating operation In the case of urgent need of domestic hot water the domestic hot water temperature set point...

Page 7: ...R refer to chapter Programming and consulting the schedule timer on page 7 What can the schedule timer do The schedule timer allows the programming of 1 Space heating and space cooling refer to Progra...

Page 8: ...in a chronological way start with action 1 for the first action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later...

Page 9: ...to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi...

Page 10: ...you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the...

Page 11: ...ode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to d...

Page 12: ...tallations with a domestic hot water tank The disinfection function disinfects the domestic hot water tank by periodically heating the domestic hot water to a specific temperature 2 00 Operation inter...

Page 13: ...Local shift value weather dependent Local shift value weather dependent The local shift value weather dependent field setting is only relevant in case weather dependent set point see field setting 1 W...

Page 14: ...restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting...

Page 15: ...related setting D Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting 03 Local shift value weather dependent 0 0 1 2 3...

Page 16: ...ed household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance wit...

Page 17: ......

Page 18: ...4PW54184 1 Copyright Daikin...

Reviews: