background image

4PW54186-1

Cop

yr

ight © Daikin

Summary of Contents for EKHBH016BA

Page 1: ...OPERATION MANUAL EKHBH016BA EKHBX016BA Indoor unit for air to water heat pump system and options...

Page 2: ...to water ERHQ or ERLQ heat pumps These units are designed for wall mounted indoor installation The units can be combined with Daikin fan coil units floor heating applications low temperature radiators...

Page 3: ...rmostat connected to the indoor unit This will prevent excessive space heating and will stop the outdoor unit and the indoor circulation pump when the room temperature is above the thermostat set poin...

Page 4: ...eration mode s space heating h space cooling c domestic water heating w or quiet mode s Within limits different modes can be combined e g space heating and domestic water heating The corresponding mod...

Page 5: ...E HEATING COOLING BUTTON This button allows manual switching between heating or cooling mode provided the unit is not a heating only unit When the unit is connected with an external room thermostat th...

Page 6: ...turns to space heating operation Space cooling operation c In this mode cooling will be activated as required by the water temperature set point Domestic water heating operation w In this mode the ind...

Page 7: ...n 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start flashing Powerful domestic water heating is deactivated automatically when the set point for the dom...

Page 8: ...rammed at 13 00 16 00 and 19 00 The last programmed command 16 00 overruled the previous programmed command 13 00 and will remain active until the next programmed command 19 00 occurs So in order to k...

Page 9: ...nt Conversely when programming cooling actions time and set point heating actions are added automatically at the same time but with the default heating set point The set points of these automatically...

Page 10: ...nds to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to step 6 By pressing the p...

Page 11: ...ram it is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press th...

Page 12: ...ep 2 through 4 to change other field settings as required 7 When finished press the z button to exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface butt...

Page 13: ...2 Start time time of the day at which the domestic hot water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature...

Page 14: ...not change this setting Leave it set to its default value C Setup on EKRP1HB digital I O PCB Solar priority mode C 00 Solar priority mode setting for information concerning the EKSOLHW solar kit refe...

Page 15: ...restart 00 Status 0 ON 0 1 4 Space heating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 35 14 35 1 C 03 Installation related setting...

Page 16: ...O PCB 00 Solar priority mode setting 0 0 1 1 01 Installation related setting 02 Installation related setting 03 Installation related setting 04 Installation related setting D Local shift value weathe...

Page 17: ...ed household waste Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance wit...

Page 18: ...NOTES NOTES...

Page 19: ......

Page 20: ...4PW54186 1 Copyright Daikin...

Reviews: