EKMBUHBA6V3

Heater kit for air to water heat pump system

4PW63549-1 – 08.2010

Installation and operation manual

5

6.3.

Installing the heater kit

At delivery, the heater kit must be checked and any damage
must be reported immediately to the carrier claims agent.

Check if all heater kit accessories (see "4. Accessories" on
page 3) are enclosed.

1

Mark the fixation positions on the wall (2 on top and 2 at the
bottom).

Make sure that the marks (2 by 2) are completely level and the
dimensions of the marks are corresponding according to
figure 1.
When the heater kit is not installed level, air might get trapped in
the water circuit resulting in malfunctioning of the heater.

2

Drill 4 holes and install 4 plugs (suitable for M6).

Plugs and screws are field supply.

3

Put the screws in the top plugs and hang the heater kit on the
top screws.

4

Put the screws in the bottom plugs and fix the 4 screws firmly.

6.4.

Connecting the water circuits

For details on connecting the water circuits and charging the system
with water refer to the outdoor unit installation manual.

1

If required (see "5.2. Safety devices" on page 4) connect a
pressure relief valve on the inlet of the heater kit (field supply,
opening pressure maximum 4 bar).

2

Connect the heater water inlet to the space heating water outlet
of the indoor unit. Connect the heater water outlet to the load.
See figure in section "3.4. General system setup" on page 3.

3

Charge the system with water.

6.5.

Field wiring

2

1

1

3

4

1

1

NOTICE

Be careful not to deform the heater piping by using
excessive force when connecting the piping.

Deformation of the piping can cause the heater to
malfunction.

NOTICE

Make sure the air purge of the heater is open (at least 2
turns).

CAUTION

A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local laws and regulations.

Switch off the power supply before making any
connections.

Use only copper wires.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
local laws and regulations.

Be sure to install the required fuses as mentioned on
the electrical wiring diagram.

The field wiring must be carried out in accordance
with the wiring diagram supplied with the heater kit
and the instructions given below.

Never squeeze bundled cables and make sure that it
does not come in contact with the piping and sharp
edges.
Make sure no external stress is applied to the terminal
connections.

Be sure to use a dedicated power supply. Never use a
power supply shared by another appliance.

Be sure to establish an earth. Do not earth the heater
kit to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.

Make sure all field wiring is insulated from the heater
kit and piping or can resist temperatures up to 90°C.

Be sure to install an earth leakage protector in
accordance with relevant local laws and regulations.
Failure to do so may cause electrical shock.

4PW58903-1A_digital.book  Page 5  Friday, September 17, 2010  11:37 AM

Summary of Contents for EKMBUHBA6V3

Page 1: ...INSTALLATION AND OPERATION MANUAL EKMBUHBA6V3 Heater kit for air to water heat pump system 4PW58903 1A_digital book Page 1 Friday September 17 2010 11 37 AM...

Page 2: ...2 170 350 376 266 500 85 220 575 1 230 535 3 200 300 500 250 350 NOTES 2 1 3 4PW58903 1A_digital book Page 1 Friday September 17 2010 11 37 AM...

Page 3: ...l Installer Technical skilled person who is qualified to install products as per the subject of this manual User Person who is owner of the product and or operates the product Service company Qualifie...

Page 4: ...e a fire Where the air contains high levels of salt Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present DANGER ELECTRICAL SHOCK S...

Page 5: ...eat exchanger 3 Pump 4 Shut off valve 5 Heater kit 6 Motorized 3 way valve optional 7 Domestic hot water tank optional 8 Collector field supply 9 By pass valve field supply 10 Radiator field supply 11...

Page 6: ...ation Therefore it is advisable to install the heater kit on a firm wall and not in nor close to a sound sensitive environment e g bedroom Do not install the heater kit in places with high humidity e...

Page 7: ...d wiring 2 1 1 3 4 1 1 NOTICE Be careful not to deform the heater piping by using excessive force when connecting the piping Deformation of the piping can cause the heater to malfunction NOTICE Make s...

Page 8: ...n International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A Item Cable bundle...

Page 9: ...7 START UP AND CONFIGURATION 7 1 Pre operation checks After the installation of the heater kit check the following before switching on the circuit breaker Filled with water Make sure that the heater...

Page 10: ...inspections on the heater kit and the field wiring have to be carried out at regular intervals This maintenance should be carried out by your local Daikin technician The described checks must be execu...

Page 11: ...ut any maintenace or repair activity always switch off the circuit breaker on the supply panel or remove the fuses Do not touch water pipes during and immediately after operation as the pipes may be h...

Page 12: ...4PW63549 1 08 2010 Copyright 2010 Daikin 4PW58903 1A_digital book Page 1 Friday September 17 2010 11 37 AM...

Reviews: