46
8.3
Other faults
8.3.1
Boiler controller is noisy when igniting
Possible causes:
Solution:
Gas supply pressure too high.
Yes
The home pressure controller may be faulty. Contact the energy company.
No
Incorrect ignition distance.
Yes
Check the ignition pin distance with the checking mold.
Replace the ignition pin.
No
Gas/air regulation not correctly configured.
Yes
Check the setting, see Gas air regulation par.7.7 and par. 7.8.
No
Weak spark.
Yes
Check the ignition pin distance with the checking mold.
Check and/or replace ignition cable.
Replace the ignition unit on the gas block. Replace the ignition pin.
8.3.2
Boiler controller resonates
Possible causes:
Solution:
Gas supply pressure too low. Lower than 20
mbar.
Yes
The home pressure controller may be faulty. Contact the energy company.
No
Recirculation combustion gases.
Yes
Check the combustion gas outlet and the air supply system.
No
Gas/air regulation not configured correctly.
Yes
Check the setting, see Gas air regulation par.7.7 and par. 7.8.
No
Boiler controller gasket faulty.
Yes
Replace the boiler controller gasket.
No
Boiler controller faulty.
Yes
Replace the boiler controller.
8.3.3
No heating (CH)
Possible causes:
Solution:
The service display shows nothing.
Yes
Check whether the plug is in the socket.
No
The service display shows nothing.
Yes
Check the fuse, see Electrical diagram par. 10.1
No
The service display shows a hyphen (
-
). The
boiler is off.
Yes
Switch on the boiler with the button.
No
Room thermostat/weather dependent regulation
not connected or faulty.
Yes
Check the wiring.
Check OpenTherm, On/off connection of the unit, or the connection between CH
boiler and RF room thermostat .Replace the thermostat.
Replace the weather-dependent regulation.
No
Pump is not running. Display shows 80 and 1.
Yes
Check the electricity supply.
Check connector X2 and X4.
No
Checking mold ignition pin position
Pin must touch test tool
Pin must not touch test tool
Summary of Contents for EKOMBG22ABV1
Page 29: ...Daikin Europe NV 31...
Page 82: ...Daikin Europe NV 31...
Page 136: ...Daikin Europe NV 32...
Page 189: ...Daikin Europe NV 31...
Page 242: ...Daikin Europe NV 32...
Page 295: ...Daikin Europe NVs GmbH 31...
Page 347: ...Daikin Europe NV 31...
Page 372: ...Daikin Europe NV 4 Daikin EKOMBG22ABV1 EKOMBG28ABV1 EKOMBG33ABV1 CH DHW O...
Page 377: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 381: ...Daikin Europe NV 13 4 2 1 2 cm O 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 382: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2...
Page 387: ...Daikin Europe NV 19 5 3 1 3 mm 1 2 A 3 1 4 2 5 6 10 2 7 8 5 3 1 X4 6 7 11 12 8 9 6 7...
Page 389: ...Daikin Europe NV 21 RF CH 5 RF CH 2 C rF L RF RF 1 5 4 4 10 1 7 5 5 5 1 1 2 2 3 4 50 mbar 5...
Page 391: ...Daikin Europe NV 23 5 2 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 398: ...Daikin Europe NV 30 5 5 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 399: ...Daikin Europe NV 31...
Page 405: ...Daikin Europe NV 37 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 406: ...Daikin Europe NV 38 7 7 1 LED CH bar q 0 Su Et q LED Eco LED LED 8 2 LED 2 LED LED LED 30...
Page 414: ...Daikin Europe NV 46 8 3 8 3 1 7 7 7 8 8 3 2 20 mbar 7 7 7 8 8 3 3 CH 10 1 OpenTherm CH RF 80...
Page 417: ...Daikin Europe NV 49 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 9 1 2 1 2 3 4 5...
Page 418: ...Daikin Europe NV 50 9 1 3 1 2 O 10 12 Nm 3 4 5 6 1 2 3 A 7 8 9 10 CH 11 12 13 14 7 7 7 8 15 16...
Page 423: ...Daikin Europe NV 55 11 Daikin Europe NV CH...
Page 424: ...008 1548499_04 05 2022 88550712...